RE 30011-B, Edition 10.2021, Bosch Rexroth AG
Product description |
Pressure and flow control system SYDFE1 series 2X, 3X
31/96
5.11.2 Switch
TD
Via switching input “Switch
Td
“ (22c) you can activate a second volume adjustment.
This function is a new feature compared with control electronics VT 5041-2X. For
more details on the function, see chapter 8 “Commissioning“ (page 59).
5.11.3 Pressure controller OFF - master/slave operation
(VT 5041-3X/1... and ...2... only)
This function is provided only for versions without power limitation.
The pressure controller can be deactivated via switching input 18a. This means
that exclusively the swivel angle control of the control electronics is active. The
deactivation of the pressure controller is signaled by LED ““ on the front
panel of the control electronics.
In addition, in conjunction with a set jumper (J4) the command value for the
swivel angle controller is no longer read in from inputs 14c and 16c, but from
inputs 18c and 20c. This function can be utilized for the master/slave operating
mode.
When the pressure controller is deactivated, the function of pressure limitation
is no longer effective.
5.11.4 Fault message
The switching output “fault message” at input 2c signals a trouble-free state with a
24-V level. When a fault is recognized, this is output as collective fault by a signal
level of 0 V at 2c. At the front panel of the control electronics, a fault message is
signaled by LED “Err.“.
Also a missing enable will lead to the generation of a fault message.
Causes for fault messages are described in chapter 15 “Troubleshooting“ (page
5.11.5 Signaling of type of control
• An active closed-loop pressure control is signaled by the yellow LED with
designation “p-control” on the front panel.
• An active closed-loop swivel angle control is signaled at connection 16a
(switching 24 V). This information is also shown on the front panel of
the control electronics (yellow LED with symbol:
).
• An active power limitation is signaled at connection 18a (switching output
+24 V). This information is also provided on the front panel of the control
electronics (yellow LED with lettering: “Power Limiter“). Available only on
version with power limitation!
5.11.6 Actual values
The normalized actual pressure value can be picked up at 24c.
The normalization of 0…+10 V is made using potentiometers R1 and R2 (front
panel). The signal is related to test jack 2.
The normalized actual swivel angle value can be picked up at 12c.
The normalization of -10...+10 V is made using potentiometers R8 and R9 (front
panel). The signal is related to test jack 4.
Fig. 10: LED indicator lamps