Fig. 7-22: F4.16 maximum pump pressure failure
Actual pressure monitoring function works all the time, no matter
when drive is in operation or standby.
7.10.4 Oil Change Warning / Error Function
Code
Name
Setting range
Default
Min.
Attri.
F4.00 Protection function config-
uration word
0...15
Bit0: Pressure sensor failure (PSF)
Bit1: Actual pressure monitoring
Bit2: p/Q max. command limit
Bit3: Oil changing detection
0
-
Run
F4.51 Warning hours of oil
change
0...60,000 hours
36,000
1
Run
F4.52 Error hours of oil change
0...60,000 hours
40,000
1
Run
F4.53 Oil in operation time
0...60,000 hours
0
-
Read
F4.54 Reset oil in operation time 0...1
0
-
Run
Tab. 7-22: Parameter list of oil change warning / error function
Oil change monitoring function can be activated by Bit3 of F4.00.
Oil operation time will be counted and saved in F4.53 when frequency converter
starts running. If this time exceeds warning or error level in [F4.51] or [F4.52],
warning or error signal will be generated. Parameter F4.54 = 1 is used to reset
the oil operation timer F4.53.
Time counter is only active during drive in operation.