126
Bosch Rexroth AG
| Tightening Technology
3 608 878 300
System 350
| 3 608 878 300/2019-03
5.2
Description of all PLC signals
The sections below provide a description of all PLC signals in alphabetic order.
5.2.1
Input signals
ActEn
Active Enable: Enables a single tightening process
Input signal used for:
•
Tightening channel (
ActEn
)
•
Communication unit in single-channel operation (
CH x.y ActEn
)
This signal enables the tightening channel for a single tightening process.
After tightening, the tightening channel is disabled for the next tightening operation until
ActEn
changes
from "high" to "low" and back to "high" again. The tightening channel is then enabled for the next
tightening. This type of enabling only enables the channel for a single tightening. The behavior of the
tightening channel depends on the assignment of the
Ch x.y En
and
Ch x.y ActEn
signals.
The following table describes the enable function in the assignment of the PLC assignment table.
AppIn 0-15
Application In Bit 0-15: Application-specific input signal
Input signal used for:
•
Tightening channel (
AppIn 0-15
)
•
Communication unit in single-channel operation (
CH x.y AppIn 0-15
)
•
Communication unit in application operation (
KE x AppIn 0-15
)
Application-specific signals are used to make special adjustments for customer requirements. They are,
e.g., suitable for looping through signals: a signal can be read by the controller via interface modules and
then output to the partner controller using the controller.
A tightening channel released via the KE with
Ch x.y ActEn
will not be blocked by removing
Ch x.y SEn
.
The tightening channel will remain released for another tightening.
In the PLC assignment table, the signal may not be applied to the
Int
interface with a channel being in
application mode. Otherwise, the following errors will be output after the application has been started:
2115 Spindle failure after start signal
and
2112 No result from tightening channel
.
Signal in PLC assignment table
Enable function
Ch x.y En
Ch x.y ActEn
Not applied
Not applied
Channel blocked.
Applied
Not applied
"High" signal enables tightening.
Not applied
Applied
Enables only a single tightening by changing from "low" to "high"
Applied
Applied
Channel is only enabled if Ch x.y En is at "high" and signal Ch x.y ActEn
has changed from "low" to "high".
In single-channel operation with activation via the KE, the
ActEn
and
En
signals must also be applied on
the INT interface of the SE PLC table according to the assignment of the KE PLC table.
Summary of Contents for Rexroth Tightening System 350
Page 4: ...4 641 Bosch Rexroth AG Schraubtechnik System 350 3 608 878 300 2019 03 ...
Page 120: ...120 641 Bosch Rexroth AG Tightening Technology 3 608 878 300 System 350 3 608 878 300 2019 03 ...
Page 194: ...194 641 Bosch Rexroth AG Tightening Technology 3 608 878 300 System 350 3 608 878 300 2019 03 ...
Page 638: ...638 641 Bosch Rexroth AG Tightening Technology 3 608 878 300 System 350 3 608 878 300 2019 03 ...