3 608 878 300
Tightening Technology |
Bosch Rexroth AG 571
System 350
| 3 608 878 300/2019-03
Configuration settings in the "RSLogix 5000" software for IMenip
Configuration of the IMenip interface module (EtherNet/IP) in the "RSLogix 5000" software of the
company Rockwell is realized using the following parameters:
•
General parameters
– Superior instance: X_1788_ENBT
– Name: IMenip
•
Connection parameter input (32 bit):
– Assembly instance: 100
– Size: 1
Ensure
that in the PLC partner control of the company Rockwell, you adjust the value of this
parameter of the configuration of the IMenip interface module. In order to ensure smooth
communication, the following parameters must in this case correspond to each other:
–
Connection parameter input
size
in the "
RSLogix 5000
"
–
Configured ranges
O send
in the BS350
Generally, the following applies:
Connection parameter input
size
=
configured ranges
O send
•
Connection parameter output (32 bit):
– Assembly instance: 150
– Size: 1
Ensure
that in the PLC partner control of the company Rockwell, you adjust the value of this
parameter of the configuration of the IMenip interface module. In order to ensure smooth
communication, the following parameters must in this case correspond to each other:
–
Connection parameter output
size
in the "
RSLogix 5000
"
–
Configured ranges
I receive
in the BS350
Generally, the following applies:
Connection parameter output
size=configured ranges
I receive
•
Connection parameter configuration (8 bit):
– Assembly instance: 1
– Size: 0
Examples of the configuration of the connection parameters
input
size
and
output
size
in the
"RSLogix 5000" software:
•
If the parameter
Configured ranges
O send
is set to the value
256 bytes
, the
connection parameter
Input
size
must be set to the following values, depending on the
communication format:
– Communication format SINT (8 bit per
size
):
256
– Communication format INT (16 bit per
size
):
128
– Communication format DINT (32 bit per
size
):
64
•
If the parameter
Configured ranges
I receive
is set to the value
256 bytes
, the
connection parameter
output
size
must be set to the following values, depending on the
communication format:
– Communication format SINT (8 bit per
size
):
256
– Communication format INT (16 bit per
size
):
128
Communication format DINT (32 bit per
size
):
64
The software "
RSLogix 5000
" of the company Rockwell is not able to read the EDS file of the Tightening
System 350. For this reason, the IMenip interface module (EtherNet/IP) must be set up as general
Ethernet module (type:
ETHERNET MODULE
| Description:
General Ethernet modules
). Detailed
information on the correct configuration is contained in section
Summary of Contents for Rexroth Tightening System 350
Page 4: ...4 641 Bosch Rexroth AG Schraubtechnik System 350 3 608 878 300 2019 03 ...
Page 120: ...120 641 Bosch Rexroth AG Tightening Technology 3 608 878 300 System 350 3 608 878 300 2019 03 ...
Page 194: ...194 641 Bosch Rexroth AG Tightening Technology 3 608 878 300 System 350 3 608 878 300 2019 03 ...
Page 638: ...638 641 Bosch Rexroth AG Tightening Technology 3 608 878 300 System 350 3 608 878 300 2019 03 ...