Wire all cables in loops. Use strain reliefs for all cables.
●
Install the operator display only vertically, with a max. deviation of ±45°,
measured from the vertical.
10.3 Mounting the built-in devices
To mount the operator display, proceed as follows:
Loss of degree of protection IP 65!
The housing, in which the operating display is installed, has to fulfill
the following conditions:
●
Free from impurities
●
Sufficient mechanical strength and flatness
These criteria influence the required IP degree of protection to a
great extent.
Further required measures have to be taken depending on the
mounting location, e. g. the stabilization of the mounting frame.
1. Prepare a mounting cut-out, refer to
chapter 10.4 "Mounting dimensions of
the built-in devices" on page 31
.
2. Insert the operator display from the front into the cut-out until the latching
lug at the top of the device latches in the cut-out.
Bosch Rexroth AG
Mounting, demounting and electric installation
VEP 15.6 Multi Touch, VEP 21.6 Multi
Touch
28/53