Valve amplifier VT-MSPA2-2X
| Commissioning
Bosch Rexroth AG, Edition 04.2020, RE 30232-01-B
Parameters
LED
indicator
lamps
Description
Editable
parameter
Output at test jack v
Command value inversion
Inv
t
G
S
Z/B
DI
Command value inversion
on/off
ON: +1 V
OFF: 0 V
Function:
Digital (enable) input DI
t
Z/B
G
S
DI
Digital (enable) input
1: Enable input
(default)
2: Inversion 2)
3: Ramp ON/OFF
2)
4: Simple ramp/
4Q ramp 2)
1
V
2 V
3 V
4 V
1) Ramp times effective only when 4Q operating mode is activated
2) The function of the digital input is XOR-linked to the internally selected state
8.6
RESTORING THE VT-MSPA2-2X TO FACTORY SETTINGS
This function is available exclusively directly upon switching on the operating
voltage. It resets all customer-specific parameters of the set valve to the factory
settings.
The module has to be de-energized.
1.
Press and hold [Set]
and switch on the supply voltage.
The LEDs signal the status shown on the left.
1.
After some time, the LEDs switch to the status shown on the left.
The module is restored to factory settings.
2.
Release [Set]
.
Restoring to factory settings is completed.