Bosch Rexroth AG |
Hydraulics
Installation and operation | RE 30523-B/09.13
4 Operating the VSPD
¾
Press and hold the “Enter“ and “ESCAPE“ keys simultaneously for at least 2
seconds until the display reads “Setup“.
9
The card is now in Configuration Mode.
¾
Press the “UP” or “DOWN” keys to select “Analog I/O”.
¾
Press
“ENTER”.
9
The card is now at the second level of the Configuration Menu, “Analog I/O“
mode.
¾
Press the “UP” or “DOWN” keys to select “Inputs”.
¾
Press
“ENTER”.
9
The menu entry Analog Input "Voltage" is shown.
¾
Press
“ENTER”.
¾
Press the “UP” or “DOWN” keys to select “Max. Value”.
¾
Press
“ENTER”.
9
The current value is shown.
¾
Press
“UP”.
This creates a positive sign. Pressing „DOWN“ gives the value a negative sign.
¾
Press “UP” until "1" is displayed.
¾
Press
“ENTER”.
¾
Press “UP” until "0" is displayed.
¾
Press
“ENTER”.
¾
Press “UP” until "." is displayed.
¾
Press
“ENTER”.
¾
Press “UP” until "0" is displayed.
¾
Press
“ENTER”.
¾
Press “UP” until "0" is displayed.
¾
Press
“ENTER”.
9
The parameter “Max. Value“ 10 Volts is now entered and displayed.
¾
Exit the Configuration Menu by pressing “ESCAPE" five times.