RE 30523-B/09.13 | Installation and operation
Hydraulics
| Bosch Rexroth AG
43/48
Faults 6
6.2 Changing the fuse
The controller card is protected against overload by means of a fuse. The fuse is of a
disposable type and has the following data:
F / 4A / 250V
______________________________________________________________
NOTE!
The fuse is defective and must be replaced!
The fuse has opened due to mechanical damage or a product de-
fect.
In this case, replace the fuse with a new one of the type indicated
above.
The fuse has opened due to external influences, i.e. due to compo-
nents connected to the controller card.
In such cases, diagnose and correct the problem that caused the
fuse to open.
Only then replace the fuse with a new one.
______________________________________________________________
Replacing the fuse on the VSPD controller card:
¾
Remove the VSPD controller card from the card holder. (reverse order as de-
scribed in chapter 2.4 Installing the card)
¾
Remove the fuse from the fuse holder without excessive force (see Fig. 19 Fuse
on the VSPD controller card).