Solution 6000
Installation Manual
Output Programming
8-7
Bosch Security Systems 07/14 BLCC610I
To initiate a medical emergency via the keypad,
simultaneously press and hold the [7] and [9] keys for 2
seconds.
44 – Keypad Fire
This event type will cause the output to operate when
a silent or audible fire alarm has been initiated from the
keypad. The output will reset when the system or area is
disarmed.
To initiate a fire emergency via the keypad,
simultaneously press and and hold the [4] and [6] keys
for 2 seconds.
45 – Keypad Panic
This event type will cause the output to operate when a
silent or audible panic alarm has been initiated from the
keypad. The output will reset when the system or area is
disarmed.
To initiate a panic emergency via the keypad,
simultaneously press and hold [1] and [3] keys.
46 – Device Tamper
This event type will cause the output to operate when
the tamper circuit on the rear of the keypad is triggered.
The output will reset when a valid user PIN is entered.
47 – Access Denied
This event type will trigger if you attempt to enter an
incorrect code more times than programmed in the pin
retry count location. The event assignment will be the
area number for this event type.
48 – Strobe
This event type is used to operate a stobe warning light.
The output can be made to operate when any of the
following events occur. At leaset one strobe event must
be selected for this output type to operate. See MENU
2-1-5 — Strobe Trigger option.
Strobe trigger options include:
= Audible Burglary Alarm
= Silent Burglary Alarm
= Fire Alarm
= Arm/Disarm Flash Via RF Keyfob
= Arm/Disarm Flash Via Keyswitch or PGM Input
= 24-Hour Alarm
49 – Smoke Sensor GND
This output is used to allow smoke detectors to be
automatically reset when the system is disarmed. You
should connect the GND terminal of all smoke detectors
in the system to outputs which are set to this event type.
For this output type to perform correctly you should
program the output polarity as type 11 - Normally
Low One Shot Open and program the output time
parameter to be 5 seconds. The smoke sensor needs to
be connected to a zone input programmed as fire.
If fire alarm verification is required, we recommend that
you program the zone pulse count tor 2 pulses and the
pulse count time to 90 seconds for each fire zone.
50 – Sensor Watch
This event type will cause the output to operate when
a zone sensor watch fault has occured. The output will
reset when the system or area in armed. See MENU 3-1-
8 — Zone Options in Section 7 - Input Programming for
more information on Sensor Watch.
51 – Senior Watch
This event type will cause the output to operate when
a Senior Watch fault has occured. See MENU 2-1-2 —
Input Options in Section 6 - Area Programming for more
information on Senior Watch.
52 – Exit Error
This event type will cause the output to operate when a
Entry/Exit Delay zone becomes unsealed during exit time
and remains unsealed when the exit time expires. The
output will reset when the system is disarmed.
53 – Keyfob Function 1
This event type will cause the output to operate when
Key X is pressed on the Keyfob. This output type is area
specific and requires a 4 button keyfob.
54 – Keyfob Function 2
This event type will cause the output to operate when
Key Y is pressed on the Keyfob. This output type is area
specific and requires a 4 button keyfob.
55 – Output In PreDelay
This event type will cause the output to operate when a
pre-delay timer is active on a different output set with a
polarity type of 01 (Normally Open, Going Low With Pre
Delay) or polarity type 08 (Normally Low, Going Open
With Pre Delay).
56 – Follow PIN Code
This event type will cause the output to operate when a
specified user PIN is entered via the keypad or when the
corresponding user’s keyfob or token is used.
You should program the User whose PIN is to be followed
into the Event Assignment for this output.
57 – Part Entry Time
This event type will cause the output to operate when
the Part Entry timer is active and will reset when Part
Entry time expires.
58 – TimeZones
This event type will cause the output to operate when a
specific time zone occurs. The output event assignment