Solution 6000
Installation Manual
System Programming
11-5
Bosch Security Systems 07/14 BLCC610I
This command will ERASE
all panel programming. To
Continue press OK, or
MENU to cancel
2)
Press [OK] to start the default process or press
[MENU] to cancel and exit.
3)
The keypad will display the following message
during the default process and will exit back to the
menu when finished.
Defaulting System
..Please Wait..
System > Commands >
Template Default
MENU 7-0-5
This command is RESERVED.
System > Commands >
TimeZone Array
-
MENU 7-0-6
This menu allows the master user and installer to view
the true/false status of all 16 timezones at the same time.
The timezone status will continuously be updated on the
display so that real time status can be seen. The top two
rows of the display show the timezone number, the third
row displays the timezone status.
T
= TimeZone is True
F
= TimeZone is False
-
= Disabled or Not Available
1)
Enter [MENU] + [7] + [0] + [6] and use the up and
down arrows to select the timezone to view. The
keypad will display the status of all 16 timezones.
0000000001111111
1234567890123456
TTTTT---FFFF----
Press
OK or MENU
In the example above,
T
= TimeZones 01 to 05 are true
F
= TimeZones 09 to 12 are false
-
= TimeZones 06 to 08 and Doors 13 to 16 are
Disabled or Not Available
2)
When finished press [OK] or [MENU] to exit.
System > Commands >
Service Mode
MENU 7-0-8
This command allows the installer to put the panel into
service mode before performing system maintenance or
upgrades. When in service mode, the following functions
are disabled. By default, service mode will automatically
terminate after 2 hours if not terminated sooner by the
installer.
Zone Tamper
Alarm Outputs
Dialler
Panel Tamper
1)
Press [MENU] + [7] + [0] + [8]. The keypad will
display the current service mode status.
Service Mode
Service Mode is OFF,
To turn ON, Press ON.
Press OK or MENU
2)
To turn service mode on, press [ON], or press [OFF]
to turn service mode off.
3)
Press [OK] or [MENU] to exit when finished.
i
Note
Service mode will automatically exit after 2 hours if
set to do so in MENU 7-7-4 — Installer Options.