background image

DS970 Series Installation Instructions

© 2011 Bosch Security Systems, Inc.

Page 3

To suspend the 1-day motion monitor timer when the control panel is
armed, apply a switched voltage to Terminal 8 as shown in the
beginning of Section 6. This will prevent the motion monitor from
timing out when no movement is anticipated. When the switched
voltage is removed from Terminal 8, the motion monitor timer will
continue to count down until motion is detected.

If the time period selected has elapsed from the last detector alarm,
a supervision trouble condition will be signaled. Refer to the
Supervision Features section for more information.

NOTE

:

If this feature has been enabled, and you wish to use the
Memory feature, the Microwave Inhibit feature will be disabled.

6.5

Trouble Memory

Short the Trouble Memory contacts with a flathead screwdriver. The
LED will indicate the last trouble condition that occurred.

7.0

Setup and Walk Tests

Select the vertical starting angle from this chart:

Mounting

Height

Standard Broad Lens

40 ft. (12 m) 70 ft. (21 m)

Long Range Lens

80 ft. (24 m) 100 ft. (30 m)

6.5 ft. (2 m)

7.5 ft. (2.3 m)
8.0 ft. (2.4 m)

-4°

-3°

-8°

-4°

-5°

-4°

-6°

-2°
-3°

-3°

-8°

-6°

DS970

To adjust the vertical starting angle for the desired mounting height
and range, loosen the vertical adjust screw and slide the board up, to
point the angle down. Note the settings on the vertical adjust scale.

Place the LED plug in the ON position and replace the cover.

7.1

Establishing PIR Pattern Coverage

Turn the Microwave range adjust to minimum.

Replace the cover and snap it into place. This will close the
tamper switch.

Wait two minutes minimum

 after applying power to start walk

tests.

NOTE

:

During the warm-up period, the tri-color LED will flash red
until the unit has stabilized (approximately 1 to 2 minutes)
and has seen no movement for two seconds. When the tri-
color LED stops flashing, the detector is ready to be tested.
With no motion in the protection area, the tri-color LED should
be OFF. If the LED is on, re-check the protection area for
disturbances affecting the microwave or PIR technologies.

Walk test 

across

 the pattern at its farthest edge, then several

times closer to the detector. Start walking from outside of the
intended protection area, and observe the tri-color LED. The edge
of the pattern is determined by the first green, PIR activation of
the LED (or the first red activation if the yellow microwave LED
activates first).

Walk test from the opposite direction to determine both
boundaries. The center of the pattern should be pointed toward
the center of the intended protection area.

NOTE

:

The pattern may be moved ±10° horizontally by rotating the
lens window left or right.

Slowly bring your arm up and into the pattern to mark the lower
boundary on PIR alarm. Perform this task at 10 to 20 ft. (3 to 6 m)
from the unit. Repeat from above for the upper boundary. 

The

center of the pattern should not be tilted upward

.

 

NOTE:

If desired coverage cannot be achieved, try angling the
coverage pattern up or down to assure the pattern is not
aimed too high or low. The angle of the PIR pattern may be
vertically positioned between -10° and +2° by loosening the
Vertical Adjust screw and sliding the circuit board up or down.
Moving the board up will angle the pattern downward.

Tighten the screw snug when positioning is completed.

7.2

Establishing Microwave Coverage

NOTE

:

It is important to wait one minute after removing/replacing
the cover so the microwave portion of the detector can settle,
and to wait at least ten seconds between the following walk
testing procedures.

The tri-color LED should be OFF before walk testing.

Walk test 

across

 the pattern at the intended coverage’s 

farthest

end. Start walking from outside the intended protection area and
observe the tri-color LED. The edge of the microwave pattern is
determined by the first yellow, microwave activation of the LED
(or the first red activation if the green PIR LED activates first).

If adequate range can not be reached, increase the Microwave
Range Adjust 

slightly

. Continue walk testing (waiting one minute

after removing/replacing the cover) and adjusting the range until
the farthest edge of desired coverage has been accurately placed.

NOTE:

Do 

not

 adjust the microwave range higher than required.

Doing so will enable the detector to catch movement outside
of the intended coverage pattern.

Walk test the unit from all directions to determine all the Microwave
pattern boundaries.  Wait at least ten seconds between walk
tests.

7.3

Establishing Detector Coverage

The tri-color LED should be OFF before walk testing.

Walk test the unit from all directions to determine the detection
boundaries. A detector alarm is signaled by the first red activation
of the tri-color LED after an initial green or yellow activation.

8.0

Meter Tests

A 20,000 Ohm/Volt (or greater) analog DC VOM is recommended. Set
the meter scale for 5 VDC (Use of the TC6000 is recommended, but
is not essential for meter use. Either outside connector pin of the
TC6000 may be used for common).

8.1

PIR Meter Readings

Connect the meter to the PIR Noise Voltage Pins.

With no target motion in the pattern, read the voltage.

NOTE:

The base reference level for PIR background noise is
approximately 1.0 VDC. Installations in quiet environments,
therefore, should result in a steady meter reading between
0.9 and 1.1 VDC.

Walk test 

across

 the farthest edge of the coverage pattern. Make

sure the detector’s cover is on.

NOTE:

Voltage changes greater than +0.75 VDC from the reference
level during walk tests 

are desirable

. If changes are less

than 0.75 VDC, the detector may fail to respond at this far of
a distance if the temperature difference between the intruder
and the background is minimal. Try adjusting the unit up
and down to maximize the voltage change during walk tests.

Summary of Contents for TriTech DS970 Series

Page 1: ...with RSS 210 of Industry and Science Canada Operation is subject to the following two conditions 1 this device may not cause harmful interference and 2 this device must accept any interference received including interference that may cause undesirable operation Changes or modifications not expressly approved by Bosch Security Systems can void the user s authority to operate the equipment 2 0 Insta...

Page 2: ... cycle NOTE During walk testing the LED will light for the first technology microwave or PIR and then light red to indicate a detector alarm The LED will not indicate activation of the second technology by lighting its color 6 0 Feature Selection 6 1 LED On Off Pins The ON position allows operation of the tri color LED If LED indication is not desired after setup and walk tests are completed place...

Page 3: ...rom the unit Repeat from above for the upper boundary The center of the pattern should not be tilted upward NOTE If desired coverage cannot be achieved try angling the coverage pattern up or down to assure the pattern is not aimed too high or low The angle of the PIR pattern may be vertically positioned between 10 and 2 by loosening the Vertical Adjust screw and sliding the circuit board up or dow...

Page 4: ...uld occur reset the detector by removing and then re applying its power The trouble condition will also be reset by the next detector alarm after a 10 second period of no alarms from either technology Motion Monitor Supervision This feature verifies that each technology has a clear view of the detection area When selected a supervision timer is activated which gives the detector the ability to ind...

Reviews: