System examples
|
49
6 720 807 794 (2013/04)
UNIMAT
9.1.4
Pipework schemes
Temperature maintaining: version with RTS return flow
temperature safeguard using return temperature
maintaining
Fig. 31 RTS return flow temperature safeguard - maintaining
D10.008 Shut-off valve
D11.006 3-way control valve
D12.001 Outlet shut-off valve
D13.007 Temperature maintaining pump
D13.010 Shut-off valve (motorised)
D13.011 Non-return valve
D13.012 Shut-off valve
10.001
Hot water flow line
11.001
Hot water return line
13.003
Shut-off valve
In temperature maintaining mode, the shut-off valve
(D10.008) in the hot water flow is open and the 3-way
control valve (D11.006) in the hot water return is closed.
In boiler mode, the temperature maintaining pump
(D13.007) is stopped and the shut-off valve on the inlet
side (D13.010) is closed.
A, B, AB: flow direction marking indicated on the 3-way
control valve.