System examples
|
51
6 720 807 794 (2013/04)
UNIMAT
High-pressure temperature maintaining: gas supply
pressure
≤
10 bar; DHW temperature
≤
110 °C
Fig. 33 Temperature maintenance
D13.013 Tee at outlet
D13.010 Shut-off valve (motorised)
D13.007 Temperature maintaining pump
D13.011 Non-return valve
D13.012 Shut-off valve
13.003
Temperature maintaining line
L
1
6 720 803 977-26.1itl
D13.013
D13.010
D13.007
D13.011 D13.012
D13.003
Temperature
maintenance
Can be used up
to boiler output
limit
Motorised
output of
temperature
maintaining
pump
Nominal diameter
Measure
ments
Shipping
weight
D13.007
1)
1) Pipe thread to DIN 2999
D13.010
1)
D13.011
1)
D13.012
1)
D13.013
2)
2) Internal diameter for flanges to DIN 2633, DIN 2634 and DIN 2635
L
1
Type
[kW]
[kW]
[DN]
[DN]
[DN]
[DN]
[DN]
[mm]
[kg]
HD 1
1000
0.06
40
20
20
20
25 / 20
579
8
HD 2
5200
0.07
40
25
25
25
32 / 25
631
10
HD 3
12600
0.19
50
32
32
32
50 / 32
676
16
HD 4
19200
0.40
50
40
40
40
50 / 40
721
20
Table 27 Specification for temperature maintenance
Dimensions given with
±
1 % tolerance;
Transport weights given with
±
3 %