Fitting
|
73
6 720 807 794 (2013/04)
UNIMAT
10.4.4
Safety valve
The safety valve from ARI, Figure 902, can be fitted
directly to the boiler connector VSL (
Fig. 13,
page 23). The internal connector diameter of the boiler
is matched to the required internal diameter of the
safety valve during manufacture. For the outlet side of
the safety valve, suitable mating flanges are available as
accessories.
Fig. 51 Safety valve for heating systems with UNIMAT UT-
L boiler
A
Outlet
a
Leg length
b
Leg height
E
Inlet
H
Height
x
Clearance above
RP 80
DN80
DN40
350
175
145
3
13
–
15
RP 100
DN100
DN50
350
175
160
4
18
–
21
RP 125
DN125
DN65
350
175
225
5
24
–
30
RP 150
DN150
DN65
350
175
240
7
32
–
40
RP 200
DN200
DN80
400
200
270
13
48
58
66
RP 250
DN250
DN100
450
225
305
23
67
83
101
RP 300
DN300
DN125
500
250
335
37
92
110
142
RP 350
DN350
DN150
550
275
405
50
125
156
192
RP 400
DN400
DN150
550
275
430
65
147
189
251
RP 500
DN500
DN200
650
325
500
123
228
278
331
1) Internal diameter for flanges to DIN 2633/2634/2635
2) Internal diameter for flanges to DIN 2633/2635
Intermediate
return piece
Nominal diameter
Measurements
Volume
Shipping weight
Type
Height
Width
PN16
PN25
PN40
A
1
1)
A
2
2)
H
1
H
2
B
[mm]
[mm]
[mm]
[l]
[kg]
[kg]
[kg]
Table 35 Specification of the intermediate return piece for UNIMAT UT-L boilers
Dimensions given with
±
1 % tolerance;
Transport weights given with
±
4 %
tolerance
x
H
b
a
E
A
6 720 642 347-64.1il
ARI safety valve,
Figure 902
Unit
Internal diameter, valve size
1)
1) Version of the flange connections; PN16 to DIN 2633 or PN40 to DIN 2635.
DN32
DN40
DN50
DN65
DN80
DN100
DN125
DN150
Internal diameter
outlet
1)
O
–
DN50
DN65
DN80
DN100
DN125
DN150
DN200
DN250
Leg length
A
mm
110
115
120
140
160
180
200
225
Leg height
b
mm
115
140
150
170
195
220
250
285
Height
H
mm
330
390
435
545
610
690
845
890
Clearance above
x
mm
200
250
300
350
400
500
500
500
Table 36 Specifications and dimensions of the safety valve for UNIMAT UT-L boilers