Fitting
UNIMAT
6 720 807 794 (2013/04)
ARI safety valve, Figure 902
Internal diameter, valve size
1)
1) Version of the flange connections; PN16 to DIN 2633 or PN40 to DIN 2635.
DN32
DN40
DN50
DN65
DN80
DN100
DN125
DN150
Maximum response pressure
Applicable for a maximum boiler output of
2)
2) Non-binding specifications - subject to change.
[bar]
[kW]
[kW]
[kW]
[kW]
[kW]
[kW]
[kW]
[kW]
2.5
565
870
1360
2300
3480
5440
7120
9900
3.0
649
1000
1560
2640
4000
6250
8190
11400
4.0
810
1250
1950
3300
5000
7800
10200
14200
5.0
960
1480
2310
3900
5910
9240
12100
16900
6.0
1100
1700
2660
4500
6820
10600
14000
19400
8.0
1390
2140
3350
5660
8580
13400
17600
24500
10.0
1670
2570
4010
6790
10300
16000
21100
29300
Table 37 Output of the safety valve for UNIMAT UT-L boilers