Condensate drain
|
83
6 720 807 794 (2013/04)
UNIMAT
For larger condensate volumes, two neutralising
systems NE 2.0 can be connected in parallel. BFor
systems with a higher output and therefore larger
condensate volumes, or for systems with dual fuel
combustion, Bosch offers a further range of neutralising
systems.
Example
For a boiler with condensing heat exchanger, boiler size
UT-L 24 (DHW inlet temperature into the condensing
heat exchanger 30 °C), approx. 200 litres of condensate
are created per hour of heating operation. A neutralising
system NE 2.0 is sufficient for this.
Fig. 59 Pump output graph for the neutralising system
NE 2.0
h
Residual head
V
Flow rate
0
10
20
30
40
50
h [m]
3,0
2,5
2,0
1,5
1,0
0,5
0
6 720 642 347-72.1il
V
[l/min]