42
en | Configuring IP Communications
AutoDome Easy IP
F01U079609 | 1.0 | 2008.08
Installation Manual
Bosch Security Systems, Inc.
1.
Launch the Configuration Manager by double-clicking the
program icon or by clicking the Start menu, scrolling to All
Programs, VIDOS, and clicking Configuration Manager.
The Configuration Manager automatically scans the
network for all Bosch Video over IP (BVIP) products. A list
of detected devices is displayed within the Network tab.
2.
Right-click the appropriate device within the Network tab.
3.
Click Unit Network Settings; the Network Settings screen
is displayed.
4.
Type the appropriate unit IP address, subnet mask, and
gateway address provided by your IT department. Click OK
when finished.
Figure 8.2
Network Settings dialog box
5.
Re-cycle power to the dome, then click refresh on the
Network tab.
8.6.3
Using the AutoDome Easy IP Web Server
The AutoDome Easy IP incorporates a network video server in
the IP module. To configure the camera using the AutoDome
Easy IP web server, proceed as follows:
1.
Set the PC to use a static, unused IP address on the same
subnet as the IP address of the dome. For example, if the
dome still has its default IP address of 192.168.0.1, and
192.168.0.10 is an unused IP address, you can set the
static IP address of the PC to 192.168.0.10.
i
NOTICE!
For more information, use the Configuration Manager manual
provided at www.boschsecurity.com.