background image

(See Figs. 9, 10 and 11).

8.1 

Plastic or steel tanks should be installed to BS5410. 

A steel tank should also conform to BS799: part 5 and be arranged
with a slope of 1 in 24 away from the outlet valve with a sludge
cock at its lower end.

8.2 

Do  not  use  galvanised  steel  tanks  or  pipework  for  the  oil

supply system.

8.3 

Do not use soldered joints on the oil supply pipework as this

could cause a hazard in the case of a fire.

8.4 

The  burners  on  all    appliances  are  supplied  so  as  to  be

connected to a single pipe gravity feed system. Details of how to
convert  the  burners  to  a  double-pipe  sub-gravity  feed  system
are shown in Fig. 9.

8.5 Oil Supply System
(a)

Single Pipe System

If a single pipe system is employed then the tank must be positioned
such that the oil level does not exceed 4 metres  above the level of
the burner oil pump and in addition the oil level must be at least 0.3
metres above the level of the oil pump. Should it prove impossible to
site the tank below the 4 metres maximum oil level a head breaking
device must be installed between the tank and the burner.

(b)

Double Pipe System

If  a  double  pipe  system  is  used  then  the  maximum  suction
height allowable is 3.5 metres.

(c)

Single Pipe Suction Lift with De-aerator

If a single pipe suction lift with a de-aerator is used, the oil tank
must  be  positioned  below  the  burner.  An  inlet  and  return  loop
should be created between the de-aerator and oil pump. The oil
pump should be connected as for a double pipe system. Details
of how to convert  to a double pipe system are shown in Fig. 9.
Oil inlet and return flexible hoses should be connected to the oil
pump inlet and return ports.
Table  10  is  a  general  guide  to  determine  the  maximum  allow-
able pipe run when using a de-aerator.
Table  10  does  not  override  the  de-aerators  manufacturers
instructions  and  should  only  be  used  in  conjunction  with  the
manufacturers instructions.
If  a  non-return  valve  is  not  incorporated  within  the  de-aerator
unit, a non-return valve should be fitted in the oil line between
the oil tank and the de-aerator.

NOTE:

If a de-aerator is used it should be fitted externally to the building.

8.6 Oil Supply Pipework
a) 

The oil supply pipe diameter can be determined using Tables 8,

9 and 10 depending on whether a single or double pipe system or
single pipe system with de-aerator is being installed. Selection of
the correct pipe diameter will depend on the position of the oil stor-
age tank relative to the burner and the length of the pipe run.

b) 

The oil supply pipe should be laid as level as possible to avoid

air pockets and unnecessary friction losses.  

c) 

The  following  components  should  be  fitted  in  the  fuel  line

between the storage tank and burner:

1. 

A manual isolating valve installed as close to the tank as possible.

2. 

A fire valve in accordance with BS5410 as shown in Fig. 10. The fire

valve should be fitted externally with a fire detection element located
within the appliance case. Use of a  capillary type valve will allow a
neat and simple installation. A suitable valve is the KBB manufactured
by Teddington Controls Limited. A spring clip has been provided
behind the electrical panel on CF/LLD models, shown in Fig. 2, and on
the burner box on RS models, shown in Fig. 3, to allow a fire valve ele-
ment to be mounted. Alternatively a fusible link or electrical system
may be used. Under no circumstances should a combination isolat-
ing/fire valve be used as the sole fire protection device.

3. 

An  oil  filter  should  be  fitted  close  to  the  oil  storage  tank.  If

there is doubt about the internal oil line condition, a further filter
should be fitted near the boiler.

11

8. Oil Supply

Fig. 9. Oil Pump.

B. Danfoss BFP 11 Oil Pump.

A. Danfoss BFP 41.

C. Suntec AS47C Oil Pump.

Cartridge filter

1

2

3

4

4a

5

6

1

2

3

4

5

6

A

1 INLET

2 RETURN

3 BLEED AND PRESSURE

GAUGE PORT

4 VACUUM GAUGE PORT

5 PRESSURE ADJUSTMENT

6 NOZZLE OUTLET

To convert to a double pipe sys-
tem,  remove  plug  4a  and  insert
the grub screw provided into the
threaded hole. Connect flow and
return pipes to (1) and (2).

To  convert  to  a  double  pipe  sys-
tem:  Remove  the  pump  front
cover,  remove  the  changeover
screw  (A)  nearest  to  ports  1  and
2,  and  the  horseshoe  washer
underneath. 

Replace 

the

changeover  screw  back  into  the
threaded  hole.  Connect  the  flow
and return pipes to 1 and 2.

Note: 

When  removing  the  pump

front cover ensure that a suitable
receptacle  is  placed  below  the
pump to catch the oil residue.

To  convert  to  a  double  pipe  sys-
tem,  remove  the  return  port  plug
(2)  and  insert  the  grub  screw  (A)
provided  into  the  threaded  hole
(B). Connect flow and return pipes
to (1) and (2).

1

2

3

3

4

5

B

A

TABLE 8 Single Pipe Gravity Feed System

MAXIMUM ALLOWABLE PIPE RUN

HEAD (metres)

(metres)

8 mm inside dia. pipe 10 mm inside dia. pipe

(10 mm O.D. copper)

(12 mm O.D. copper)

0.5

12

30

1.0

25

69

1.5

37

91

2.0

49

100

2.5

62

100

3.0

74

100

3.4

87

100

4.0

99

100

TABLE 9 Double Pipe Sub-Gravity Feed System

MAXIMUM ALLOWABLE PIPE RUN

HEAD (metres)

(metres)

8 mm inside dia. pipe 10 mm inside dia. pipe

(10 mm O.D. copper)

(12 mm O.D. copper)

0

50

100

0.5

44

100

1.0

38

95

1.5

32

80

2.0

26

66

2.5

20

51

3.0

14

37

3.5

8

22

All manuals and user guides at all-guides.com

all-guides.com

Summary of Contents for Worcester Danesmoor 12/14

Page 1: ...ater and Central Heating 12 14 MINIMUM 12 kW 41 000 Btu h MAXIMUM 14 kW 48 000 Btu h 15 19 MINIMUM 15 kW 51 000 Btu h MAXIMUM 19 kW 65 000 Btu h 20 25 MINIMUM 20 kW 68 000 Btu h MAXIMUM 25 kW 85 000 Btu h THESE INSTRUCTIONS APPLY TO UK MODELS ONLY THESE INSTRUCTIONS ARE TO BE LEFT WITH THE APPLIANCE All manuals and user guides at all guides com a l l g u i d e s c o m ...

Page 2: ...as not fulfilled his obligations to record the information required by the initiative It is important that The services and the system are properly flushed as specified The User is clearly instructed on the correct operation of the appliance The benefits of regular servicing are explained to maintain the efficiency and extend the life of the appliance 2 1 These instructions cover both conventional...

Page 3: ...r circumstances Central Heating and Hot Water Mode The appliance will supply heat to the central heating system as required The water supplied to the central heating circuit can be set to the desired temperature by adjusting the heating control thermostat located on the facia panel SPECIFICATIONS Model 12 14 15 19 20 25 POWER SUPPLY 230V 50 Hz 230V 50 Hz 230V 50 Hz IP RATING IP 20 IP20 IP 20 HEATI...

Page 4: ... kW Btu hr kW Btu hr Output Kg h l h 28 Sec Kerosene 0 50 60 ES 110 1 40 1 77 215 10 5 8 5 17 58 000 15 51 000 28 Sec Kerosene 0 55 80 EH 115 1 59 2 01 225 10 5 8 75 19 65 000 17 58 000 28 Sec Kerosene 0 60 60 ES 105 1 78 2 25 235 11 5 9 0 21 5 73 000 19 65 000 35 Sec Gas Oil 0 50 80 S 155 1 80 2 12 235 11 5 9 0 21 5 73 000 19 65 000 NOMINAL BOILER RATING AT NORMAL OPERATING TEMPERATURE 15 19 Tabl...

Page 5: ...efficient combustion an adequate supply of air must be delivered to the combustion chamber To provide sufficient air a suitable inlet should be provided into the room or space in which the boiler is situated the sizes of which are given in Table 5 An air brick or other form of continuous air supply may have to be built into the installation in order to ensure an adequate supply of air 6 2 If the a...

Page 6: ...screw Pressure relief valve Central heating flow Pump Burner Front panel Expansion vessel Electrical panel User operating switch Optional programmer position Top panel Thermostat knob Fire valve clip Manual reset over heat thermostat phial Automatic reset high limit thermostat phial Control thermostat phial Split pin Control Box Assembly All manuals and user guides at all guides com a l l g u i d ...

Page 7: ...e relief valve Central heating flow Pump Burner Front panel Expansion vessel Electrical panel User operating switch Optional programmer position Top panel Thermostat knob Fire valve clip Burner cover Rear air duct Rear air duct access cover Manual reset over heat thermostat phial Automatic reset high limit thermostat phial Control thermostat phial Split pin Control Box Assembly All manuals and use...

Page 8: ...terminal arrangement 7 3 Room Sealed Balanced Flue Model RS The appliance is supplied ready for installation as a low level discharge balanced flue system by the simple addition of one of the flue terminal kit options shown in Fig 6 Details of the installation procedure are included in the Flue Terminal Installation instructions supplied with the terminal kit Alternatively a range of room sealed b...

Page 9: ...Discharge 4 to 7 Single Skin Wall For use with non standard single skin walls up to 182 mm thick Where noise emission from the flue terminal is likely to be of concern it is recommended that the standard 12 in terminal is used and the appliance stood away from the wall to take up the extra terminal body length c Rear Discharge Extension Kit 12 to 36 Wall X For use where the wall thickness exceeds ...

Page 10: ...nal facing the terminal Not allowed 1200 K Vertically from a terminal on the same wall Not allowed 1500 L Horizontally from a terminal on the same wall Not allowed 750 M Above an intersection with the roof 600 Not applicable 732 N From a vertical structure on the side of the terminal 750 Not applicable 750 O Above a vertical structure less than 750mm from the side of the terminal 600 Not applicabl...

Page 11: ...b The oil supply pipe should be laid as level as possible to avoid air pockets and unnecessary friction losses c The following components should be fitted in the fuel line between the storage tank and burner 1 A manual isolating valve installed as close to the tank as possible 2 A fire valve in accordance with BS5410 as shown in Fig 10 The fire valve should be fitted externally with a fire detecti...

Page 12: ...um Fire valve to BS 5410 Fire valve to BS 5410 Isolating valve Isolating valve Fire detection element Filter Burner Burner Wall Wall b Double pipe system Isolating valve Non return valve Non return valve Fire detection element Isolating valve Oil tank c Single pipe lift system with de aerator Fire valve to BS 5410 H 3 5 m 11 5 ft maximum Burner Wall Fire detection element De aerator H 3 5 m 11 5 f...

Page 13: ...tems when all of the radiators are fitted with thermostatic radiator valves 9 5 The pressure jet burner fitted to the appliance has full auto matic control and hence there is no requirement for heat leak radiators 9 6 Any unused boiler tappings should be plugged prior to filling 9 7 The primary system should be flushed and treated in accordance with the recommendations of BS 7593 before the system...

Page 14: ...The filling point must be at low level and must never be a permanent direct fixing to the mains water supply 9 16 Water loss must be replaced See Fig 13 The connection should be made to the central heating return as close to the appliance as possible 9 17 The make up vessel where fitted must be fitted with a non return valve 9 18 Repeated venting loses water from the system It is essential that th...

Page 15: ...16a A plug in colour co ordinated 2 channel electronic programmer is available from Worcester Heat Systems Limited Full instructions covering installation and operation of the programmer are included with the kit The programmer will give fully independent central heating CH and hot water HW programmes when the switch on the rear of the unit is set to P If an external programmer is to be fitted to ...

Page 16: ...ations having pumped circulation to both the domestic hot water and radiator circuits The domestic hot water and radiator circuits are independently controlled by two motorised valves via a cylinder thermostat and a room thermostat Both thermostats switch the water circulator and the boiler on and off 10 9 Honeywell Y Plan See Fig 19 The Y Plan provides complete control on installations having pum...

Page 17: ... 1 to 3 and link 2 to 4 and make link 3 to 4 10 WAY JUNCTION BOX NOTE If a frost thermostat is required it can be wired to the remote junction box NOTE The 10 way junction box must be a terminal block type and current rated to at least 5 amps Remote Pre wired Junction Box OUTSIDE BOILER INSIDE BOILER 7 8 910 X External Pump disconnect and remove Pump supplied in boiler NOTE Optional Worcester Prog...

Page 18: ...ve link 1 to 3 and link 2 to 4 and make link 3 to 4 Grey White Blue Brown Room thermostat Pump supplied in boiler N E NL HEAT SYSTEMS HEATING ADVANCE OFF TWICE ONCE ON OFF TWICE ONCE ON SELECT LOCK SET YES SELECT PM TUE HOT WATER ADVANCE Burner Socket Optional Worcester Programmer Cylinder Thermostat C 1 2 Mid Position Valve Honeywell V4073A E N L N E E N 1 2 3 4 5 6 7 8 9 1112131415 10 Blue Brown...

Page 19: ...ith the open grommet supplied in the plastic bag 4 Slacken the pipe retaining clip screw located directly below the grommet hole When using 12mm copper pipe replace the clip with the larger one supplied 5 Bend a piece of 10mm or 12mm copper tube as selected to the correct profile to allow the pipe to be fed down the side of the appli ance Make a slight chamfer on the end of the pipe to be fed thro...

Page 20: ... using a 5mm Allen key Note It is important that a good seal is made between the burner and the boiler to prevent re circulation of the flue gases from the combustion chamber to the burner inlet or the room in the case of a CF LLD appliance 3 On the RS balanced flue model feed the electrical lead back through the hole in the burner surround housing and fit the grom met into the hole ensuring a sea...

Page 21: ...e correctly located If the baffles are correctly located then reduce the pump pressure since nozzle variations of up to or 15 may occur 12 15 Remove the oil pressure gauge and manifold and check all oil system joints for any signs of leakage 12 16 On the RS balanced flue model fit the burner cover box supplied in the flue terminal kit by lining up the four ball studs and the polarising pin in the ...

Page 22: ... nozzle line and rotate the adjusting disc one turn anti clockwise to move forward by 1 mm Output Dimension kW Head Type A 15 PL 6 7 21 5 10 3 mm 17 PL 6 7 21 5 10 5 mm 19 PL 6 7 21 5 10 5 mm Fig 22 Electro Oil Inter B11 Burner 20 25 model Combustion Head Air control indicator Photocell Air adjustment screw 4 mm hexagonal head Transformer Control box Oil pump Pressure adjustment screw Draught tube...

Page 23: ... 2 Pre Service Check 1 Remove the cabinet front and top panels as described in Section 5 2 On the RS balanced flue model remove the burner cover box as described in Section 5 5 3 Operate the appliance and system noting any faults which may need to be corrected during the service 14 3 Cleaning the Burner IMPORTANT Disconnect the electrical supply at the mains before commencing any servicing Turn of...

Page 24: ...e of a CF LLD appliance 14 4 Remove the paper element from the external oil filter and replace If the filter contains a washable element then thoroughly clean in Kerosene or white spirit and re assemble into the filter 14 5 Clean the air ducts RS balanced flue model only 1 Remove the rear duct top cover 2 Shine a light down the rear duct and inspect both the rear and under duct for any sign of deb...

Page 25: ...ogrammer open circuit Check by linking 8 and 9 on the connector Faulty control box Replace if necessary Flue draught incorrect Check flue draught Combustion settings incorrect Set up as in installation instructions Faulty nozzle Replace nozzle HIGH SMOKE NUMBER Faulty nozzle Replace nozzle Incorrect combustion settings Readjust as in installation instructions Oil pressure incorrect Adjust to recom...

Page 26: ...ox Base Satronic S01 S701 1 8 716 142 782 0 Ignition Electrode 1 8 716 142 752 0 Motor B9 AEG or Simel 70 W 1 8 716 156 597 0 Motor B11 AEG FHP 90W 1 8 716 142 732 0 Oil Pump B9 Danfoss BFP41L3 1 8 716 142 743 0 Oil Pump B11 Danfoss BFP11L3 1 8 716 142 736 0 Transformer Danfoss EBI 052F0030 excludes cable 1 8 716 156 696 0 Mechanical Shut Off Valve 1 8 716 156 658 0 Flexible Oil Line Kit WHS 1 8 7...

Page 27: ...27 All manuals and user guides at all guides com ...

Page 28: ...inued improvement All goods sold are subject to our official Conditions of Sale a copy of which may be obtained on application 8 716 114 733a 11 07 Worcester Heat Systems Limited Bosch Group Cotswold Way Warndon Worcester WR4 9SW Telephone 01905 754624 Fax 01905 754619 Technical Helpline 08705 266241 www worcester bosch co uk All manuals and user guides at all guides com ...

Reviews: