background image

11.1 

After  unpackaging  the  appliance  it  is  recommended  that  all

cabinet panels are removed, as described in Section 5, and stored in
a  safe  place  to  avoid  damage  during  installation  and  allow  easy
inspection for any leaks after the system has been filled.

11.2 

Remove  the  burner  as  described  below  and  store  in  a  safe

place until the appliance is ready for commissioning.

(a) Conventional Flue Appliance (CF/LLD)

1. 

Remove  the  electrical  lead  plug  by  depressing  the  two  locking

ears and pulling the plug downwards.

2. 

Remove  the  burner  from  the  boiler  by  slackening  the  two  M6

retaining screws located in the burner housing ring and pulling the
burner clear. This will require the use of a 5mm allen key.

(b) Room Sealed Balance Flue Appliance (RS).
1. 

Remove  the  burner  box  cover  by  pulling  forwards  to  release  the

ball studs. This will be found easier by pulling on the side of the han-
dle  first  to  release  two  of  the  ball  studs  and  then  repeating  on  the
other side. Take care not to pivot the remaining two ball studs too far
around as this will cause damage to the spring clips.

2. 

Remove  the  electrical  lead  plug  by  depressing  the  two  locking

ears and pulling the plug.

3. 

Push  the  electrical  lead  grommet  back  through  the  burner  sur-

round box and feed the lead through the hole.

4. 

Remove  the  burner  from  the  boiler  by  slackening  the  two  M6

retaining screws located in the burner housing ring and pulling the
burner clear. This will require the use of a 5mm allen key.

11.3 Flue system installation.

Install the appliance flue system as described in Section 7.

11.4 Heating system installation.

Before the appliance is fitted to the heating system

flush the system and mains water supply.

1. 

Plumb the boiler into the central heating system. 

2. 

Check that all unused sockets have been plugged.

3. 

Fill the system and vent all radiators and high points to remove

air from the system.

4. 

Check the boiler and all pipework connections for leaks.

11.5 Oil supply installation.

(See Figs. 9 to 11).

NOTE:

Never route the oil supply pipe/hose directly below the com-

bustion chamber base.

NOTE: 

Connection of rigid copper pipe to the oil pump is not recom-

mended. Connection to the oil pump should be made with flexible
oil hoses as shown in Fig. 11.

(a) Single pipe suction lift with de-aerator.

For connection of single pipe suction lift with de-aerator follow the
proceedure as for a double pipe system as described below.

(b) Double pipe system oil return pipe.

When  fitting  an  RS  balanced  flue  appliance  follow  steps  1  to  11.
When fitting a CF/LLD appliance follow step 1 and fit a bulkhead fit-
ting to the bracket for the return pipe and continue from step 10.

1. 

Remove  the  isolating  valve  bulkhead  fitting  by  unscrewing  the

locknut on the underside.

2. 

Remove the blind grommet from the fixed burner surround box

and discard.

3. 

Replace  the  blind  grommet  with  the  open  grommet  supplied  in

the plastic bag.

4. 

Slacken  the  pipe  retaining  clip  screw  located  directly  below  the

grommet hole. When using 12mm copper pipe replace the clip with
the larger one supplied.

5. 

Bend a piece of 10mm or 12mm copper tube ( as selected ) to the

correct profile to allow the pipe to be fed down the side of the appli-
ance.  Make  a  slight  chamfer  on  the  end  of  the  pipe  to  be  fed
through the grommet to facilitate easy insertion.

6. 

Lubricate  the  grommet  hole  with  vaseline  (or  butter  etc.)  and

slide  the  pipe  through  the  hole,  supporting  the  grommet  on  its
underside to prevent it dislodging.

7. 

Feed the pipe through the retaining clip, allowing approximately

80 mm of pipe to project beyond the clip, and tighten the retaining
screw. Take care not to overtighten the screw!

8. 

Hold  the  pipe  at  the  retaining  clip  and  gently  pull  the  pipe

forward sufficiently to allow a compression to 1/4 inch BSP female
fitting to be fitted for connection to the oil return flexible hose.

9. 

Connect the fitting to the pipe and fit a 1/4 inch BSP taper thread

flexible  hose,  ensuring  a  good  seal  using  PTFE  tape  or  suitable  oil
sealing  compound.  The  flexible  hose  should  have  a  1/4  inch  BSP
rotating union taper fitting at the other end with a 90 degree bend
and 1/4 inch BSP nipple for connection to the oil pump.

10. 

Replace the isolating valve bulkhead fitting. 

11. 

Fit the oil supply pipe as described in the following section.

(c) Single pipe system oil supply pipe.
1. 

Bend a piece of 10mm or 12mm copper tube (as selected) to the

correct profile to allow the pipe to be fed down the side of the appli-
ance. The pipe may be routed along either the right or left hand
side of the boiler as required. When using 12mm pipe fit a 12mm
to 10mm compression coupling and connect to the valve with a
short piece of 10 mm pipe, otherwise connect direct to the valve.

Note: 

never use soldered joints on oil supply pipes as this could

cause a hazard in the case of a fire.

2. 

Route the pipe back to the oil supply tank ensuring that it is

hard against the boiler, to allow installation of the side panel.

3. 

With the isolating valve in the correct orientation tighten the

back-nut.

4. 

Turn the isolating cock fully clockwise to close the valve.

5. 

Open the main oil supply valve at the tank and check for any leaks.

6. 

Place  a  suitable  container  below  the  bulkhead  fitting  and

open the valve.

7. 

Draw  off  at  least  2.5  litres  of  oil  until  a  steady  flow  of  clear

uncontaminated oil can be seen and turn off the isolating valve.

Note: 

This  method  may  not  be  possible  on  some  installations

where  a  sub-gravity  system  is  used.  Where  this  problem  arises
bleed the system using the oil pump as described in Section 12
and remove and clean the oil pump filter to remove any debris
collected as a result of installation.

11.6 

Replace  the  electrical  control  panel  and  side  panels  in

reverse order to the removal procedure of Section 5 and connect
the electrical supply as described in Section 10.

11. Installation

19

All manuals and user guides at all-guides.com

Summary of Contents for Worcester Danesmoor 12/14

Page 1: ...ater and Central Heating 12 14 MINIMUM 12 kW 41 000 Btu h MAXIMUM 14 kW 48 000 Btu h 15 19 MINIMUM 15 kW 51 000 Btu h MAXIMUM 19 kW 65 000 Btu h 20 25 MINIMUM 20 kW 68 000 Btu h MAXIMUM 25 kW 85 000 Btu h THESE INSTRUCTIONS APPLY TO UK MODELS ONLY THESE INSTRUCTIONS ARE TO BE LEFT WITH THE APPLIANCE All manuals and user guides at all guides com a l l g u i d e s c o m ...

Page 2: ...as not fulfilled his obligations to record the information required by the initiative It is important that The services and the system are properly flushed as specified The User is clearly instructed on the correct operation of the appliance The benefits of regular servicing are explained to maintain the efficiency and extend the life of the appliance 2 1 These instructions cover both conventional...

Page 3: ...r circumstances Central Heating and Hot Water Mode The appliance will supply heat to the central heating system as required The water supplied to the central heating circuit can be set to the desired temperature by adjusting the heating control thermostat located on the facia panel SPECIFICATIONS Model 12 14 15 19 20 25 POWER SUPPLY 230V 50 Hz 230V 50 Hz 230V 50 Hz IP RATING IP 20 IP20 IP 20 HEATI...

Page 4: ... kW Btu hr kW Btu hr Output Kg h l h 28 Sec Kerosene 0 50 60 ES 110 1 40 1 77 215 10 5 8 5 17 58 000 15 51 000 28 Sec Kerosene 0 55 80 EH 115 1 59 2 01 225 10 5 8 75 19 65 000 17 58 000 28 Sec Kerosene 0 60 60 ES 105 1 78 2 25 235 11 5 9 0 21 5 73 000 19 65 000 35 Sec Gas Oil 0 50 80 S 155 1 80 2 12 235 11 5 9 0 21 5 73 000 19 65 000 NOMINAL BOILER RATING AT NORMAL OPERATING TEMPERATURE 15 19 Tabl...

Page 5: ...efficient combustion an adequate supply of air must be delivered to the combustion chamber To provide sufficient air a suitable inlet should be provided into the room or space in which the boiler is situated the sizes of which are given in Table 5 An air brick or other form of continuous air supply may have to be built into the installation in order to ensure an adequate supply of air 6 2 If the a...

Page 6: ...screw Pressure relief valve Central heating flow Pump Burner Front panel Expansion vessel Electrical panel User operating switch Optional programmer position Top panel Thermostat knob Fire valve clip Manual reset over heat thermostat phial Automatic reset high limit thermostat phial Control thermostat phial Split pin Control Box Assembly All manuals and user guides at all guides com a l l g u i d ...

Page 7: ...e relief valve Central heating flow Pump Burner Front panel Expansion vessel Electrical panel User operating switch Optional programmer position Top panel Thermostat knob Fire valve clip Burner cover Rear air duct Rear air duct access cover Manual reset over heat thermostat phial Automatic reset high limit thermostat phial Control thermostat phial Split pin Control Box Assembly All manuals and use...

Page 8: ...terminal arrangement 7 3 Room Sealed Balanced Flue Model RS The appliance is supplied ready for installation as a low level discharge balanced flue system by the simple addition of one of the flue terminal kit options shown in Fig 6 Details of the installation procedure are included in the Flue Terminal Installation instructions supplied with the terminal kit Alternatively a range of room sealed b...

Page 9: ...Discharge 4 to 7 Single Skin Wall For use with non standard single skin walls up to 182 mm thick Where noise emission from the flue terminal is likely to be of concern it is recommended that the standard 12 in terminal is used and the appliance stood away from the wall to take up the extra terminal body length c Rear Discharge Extension Kit 12 to 36 Wall X For use where the wall thickness exceeds ...

Page 10: ...nal facing the terminal Not allowed 1200 K Vertically from a terminal on the same wall Not allowed 1500 L Horizontally from a terminal on the same wall Not allowed 750 M Above an intersection with the roof 600 Not applicable 732 N From a vertical structure on the side of the terminal 750 Not applicable 750 O Above a vertical structure less than 750mm from the side of the terminal 600 Not applicabl...

Page 11: ...b The oil supply pipe should be laid as level as possible to avoid air pockets and unnecessary friction losses c The following components should be fitted in the fuel line between the storage tank and burner 1 A manual isolating valve installed as close to the tank as possible 2 A fire valve in accordance with BS5410 as shown in Fig 10 The fire valve should be fitted externally with a fire detecti...

Page 12: ...um Fire valve to BS 5410 Fire valve to BS 5410 Isolating valve Isolating valve Fire detection element Filter Burner Burner Wall Wall b Double pipe system Isolating valve Non return valve Non return valve Fire detection element Isolating valve Oil tank c Single pipe lift system with de aerator Fire valve to BS 5410 H 3 5 m 11 5 ft maximum Burner Wall Fire detection element De aerator H 3 5 m 11 5 f...

Page 13: ...tems when all of the radiators are fitted with thermostatic radiator valves 9 5 The pressure jet burner fitted to the appliance has full auto matic control and hence there is no requirement for heat leak radiators 9 6 Any unused boiler tappings should be plugged prior to filling 9 7 The primary system should be flushed and treated in accordance with the recommendations of BS 7593 before the system...

Page 14: ...The filling point must be at low level and must never be a permanent direct fixing to the mains water supply 9 16 Water loss must be replaced See Fig 13 The connection should be made to the central heating return as close to the appliance as possible 9 17 The make up vessel where fitted must be fitted with a non return valve 9 18 Repeated venting loses water from the system It is essential that th...

Page 15: ...16a A plug in colour co ordinated 2 channel electronic programmer is available from Worcester Heat Systems Limited Full instructions covering installation and operation of the programmer are included with the kit The programmer will give fully independent central heating CH and hot water HW programmes when the switch on the rear of the unit is set to P If an external programmer is to be fitted to ...

Page 16: ...ations having pumped circulation to both the domestic hot water and radiator circuits The domestic hot water and radiator circuits are independently controlled by two motorised valves via a cylinder thermostat and a room thermostat Both thermostats switch the water circulator and the boiler on and off 10 9 Honeywell Y Plan See Fig 19 The Y Plan provides complete control on installations having pum...

Page 17: ... 1 to 3 and link 2 to 4 and make link 3 to 4 10 WAY JUNCTION BOX NOTE If a frost thermostat is required it can be wired to the remote junction box NOTE The 10 way junction box must be a terminal block type and current rated to at least 5 amps Remote Pre wired Junction Box OUTSIDE BOILER INSIDE BOILER 7 8 910 X External Pump disconnect and remove Pump supplied in boiler NOTE Optional Worcester Prog...

Page 18: ...ve link 1 to 3 and link 2 to 4 and make link 3 to 4 Grey White Blue Brown Room thermostat Pump supplied in boiler N E NL HEAT SYSTEMS HEATING ADVANCE OFF TWICE ONCE ON OFF TWICE ONCE ON SELECT LOCK SET YES SELECT PM TUE HOT WATER ADVANCE Burner Socket Optional Worcester Programmer Cylinder Thermostat C 1 2 Mid Position Valve Honeywell V4073A E N L N E E N 1 2 3 4 5 6 7 8 9 1112131415 10 Blue Brown...

Page 19: ...ith the open grommet supplied in the plastic bag 4 Slacken the pipe retaining clip screw located directly below the grommet hole When using 12mm copper pipe replace the clip with the larger one supplied 5 Bend a piece of 10mm or 12mm copper tube as selected to the correct profile to allow the pipe to be fed down the side of the appli ance Make a slight chamfer on the end of the pipe to be fed thro...

Page 20: ... using a 5mm Allen key Note It is important that a good seal is made between the burner and the boiler to prevent re circulation of the flue gases from the combustion chamber to the burner inlet or the room in the case of a CF LLD appliance 3 On the RS balanced flue model feed the electrical lead back through the hole in the burner surround housing and fit the grom met into the hole ensuring a sea...

Page 21: ...e correctly located If the baffles are correctly located then reduce the pump pressure since nozzle variations of up to or 15 may occur 12 15 Remove the oil pressure gauge and manifold and check all oil system joints for any signs of leakage 12 16 On the RS balanced flue model fit the burner cover box supplied in the flue terminal kit by lining up the four ball studs and the polarising pin in the ...

Page 22: ... nozzle line and rotate the adjusting disc one turn anti clockwise to move forward by 1 mm Output Dimension kW Head Type A 15 PL 6 7 21 5 10 3 mm 17 PL 6 7 21 5 10 5 mm 19 PL 6 7 21 5 10 5 mm Fig 22 Electro Oil Inter B11 Burner 20 25 model Combustion Head Air control indicator Photocell Air adjustment screw 4 mm hexagonal head Transformer Control box Oil pump Pressure adjustment screw Draught tube...

Page 23: ... 2 Pre Service Check 1 Remove the cabinet front and top panels as described in Section 5 2 On the RS balanced flue model remove the burner cover box as described in Section 5 5 3 Operate the appliance and system noting any faults which may need to be corrected during the service 14 3 Cleaning the Burner IMPORTANT Disconnect the electrical supply at the mains before commencing any servicing Turn of...

Page 24: ...e of a CF LLD appliance 14 4 Remove the paper element from the external oil filter and replace If the filter contains a washable element then thoroughly clean in Kerosene or white spirit and re assemble into the filter 14 5 Clean the air ducts RS balanced flue model only 1 Remove the rear duct top cover 2 Shine a light down the rear duct and inspect both the rear and under duct for any sign of deb...

Page 25: ...ogrammer open circuit Check by linking 8 and 9 on the connector Faulty control box Replace if necessary Flue draught incorrect Check flue draught Combustion settings incorrect Set up as in installation instructions Faulty nozzle Replace nozzle HIGH SMOKE NUMBER Faulty nozzle Replace nozzle Incorrect combustion settings Readjust as in installation instructions Oil pressure incorrect Adjust to recom...

Page 26: ...ox Base Satronic S01 S701 1 8 716 142 782 0 Ignition Electrode 1 8 716 142 752 0 Motor B9 AEG or Simel 70 W 1 8 716 156 597 0 Motor B11 AEG FHP 90W 1 8 716 142 732 0 Oil Pump B9 Danfoss BFP41L3 1 8 716 142 743 0 Oil Pump B11 Danfoss BFP11L3 1 8 716 142 736 0 Transformer Danfoss EBI 052F0030 excludes cable 1 8 716 156 696 0 Mechanical Shut Off Valve 1 8 716 156 658 0 Flexible Oil Line Kit WHS 1 8 7...

Page 27: ...27 All manuals and user guides at all guides com ...

Page 28: ...inued improvement All goods sold are subject to our official Conditions of Sale a copy of which may be obtained on application 8 716 114 733a 11 07 Worcester Heat Systems Limited Bosch Group Cotswold Way Warndon Worcester WR4 9SW Telephone 01905 754624 Fax 01905 754619 Technical Helpline 08705 266241 www worcester bosch co uk All manuals and user guides at all guides com ...

Reviews: