background image

21

boiler is shut down. The lockout indicator light in the boiler control
panel will illuminate indicating that the burner has gone to lockout.
In this instance wait two minutes and press the lockout reset button
mounted in the burner control box. Another start sequence is then
initiated. Repeat the procedure until a flame is established.

Note: 

Persistent  lockout  when  running  indicates  a  fault  and  a

Service Engineer should be consulted.

12.11 

Run  the  boiler  for  approximately  3  minutes  and  switch

off checking that there is no after-spurting from the nozzle. This
can be detected by oil saturation on the blast tube. If after-spurt-
ing occurs remove the burner from the boiler, unscrew the noz-
zle,  and  while  holding  the  burner  in  a  vertical  position,  fill  the
nozzle holder with oil. Refit the burner and continue to run the
boiler for three minute periods until after-spurting stops.

Note: 

In  order  that  after-spurting  is  reduced  to  a  minimum

during  the  commissioning  period  it  is  recommended  that  a
pressure gauge only is fitted on the external pressure gauge port
on the Electro Oil B11 (See Fig. 22). Use of a “T” piece pressure
gauge  manifold  will  increase  the  oil  line  volume  and  hence
increase the degree of after-spurting.

12.12 

Run  the  boiler  for  a  further  15  minute  period  and  then

finally fine tune the air shutter setting to give the CO

2

level speci-

fied  in  Tables  2  to  4  less  0.5%  CO

2

.  During  this  period  some

smoke will be emitted due to the burning of the organic binder
in  the  base  insulation  board.  Smoke  readings  will  therefore  be
inaccurate at this point.

Note: 

A  flue  gas  sampling  point  is  located  on  the  boiler  top

plate.

12.13 

Check that the smoke reading is in the range 0-1. If this

cannot  be  achieved  then  check  that  the  burner  head  is  set
correctly and the nozzle is in good condition.

12.14 

Check  that  the  flue  temperature  does  not  exceed  the

value specified in Tables 2 to 4. If this is the case then check that
the  baffles  are  correctly  located.  If  the  baffles  are  correctly
located  then  reduce  the  pump  pressure  since  nozzle  variations
of up to + or – 15% may occur.

12.15 

Remove  the  oil  pressure  gauge  and  manifold  and  check

all oil system joints for any signs of leakage.

12.16 

On  the  RS  balanced  flue  model  fit  the  burner  cover  box

supplied in the flue terminal kit by lining up the four ball studs
and  the  polarising  pin  in  the  top  flange  of  the  box  and  firmly
pushing  forward.  Check  that  the  cover  is  properly  seated  by
pressing forwards on the front top and then bottom face of the
box to ensure a room seal is achieved.

On the CF/LLD model fit the cabinet front panel.

12.17 

Allow  the  burner  to  run  for  a  further  five  minutes  and

then recheck the CO

2

level and adjust the air setting if required.

With the burner cover/panel fitted as 12.16, repeat the previous
test procedure and check that the smoke number is in the range
0-1. Repeat the fine tuning procedure if found necessary.

12.18 

Refit the cabinet top and front panels in the reverse order 

to that described in Section 5.

12.19

When the heating circuit has reached full operating  tem-

perature check the whole system for any leaks.

12.20

Add  a  suitable  proprietary  corrosion  inhibitor  such  as

Fernox or Sentinel. This will inhibit corrosion, protect the circu-
lating pump and valves and reduce the possibility of “Kettling”
noises resulting from deposits of scale and sludge in the boiler.
Refer to the product manufacturers instructions for further infor-
mation.

Output

Dimension

kW

Head Type

A

12

PL 6/7/21.5/10-E

3 mm

14

PL 6/7/21.5/10-E

5 mm

Fig. 20. Electro Oil Inter B9A Burner.

(12/14 model)

Combustion Head

Combustion head

Locking screw

Transformer

Photocell

Control box

Lockout reset button

Air adjustment screw

(4mm hexagonal head)

Air control indicator

Oil pump

Pressure Adjustment
Screw

Adjusting
disc

To adjust the nozzle position, undo the
locking screw located at the rear of the
nozzle line and rotate the adjusting
disc one turn anti-clockwise to move
forward by 1 mm.

Nozzle block

2mm

Nozzle

10mm

Draught tube

Spark gap

2.0-2.5 mm

A

All manuals and user guides at all-guides.com

all-guides.com

Summary of Contents for Worcester Danesmoor 12/14

Page 1: ...ater and Central Heating 12 14 MINIMUM 12 kW 41 000 Btu h MAXIMUM 14 kW 48 000 Btu h 15 19 MINIMUM 15 kW 51 000 Btu h MAXIMUM 19 kW 65 000 Btu h 20 25 MINIMUM 20 kW 68 000 Btu h MAXIMUM 25 kW 85 000 Btu h THESE INSTRUCTIONS APPLY TO UK MODELS ONLY THESE INSTRUCTIONS ARE TO BE LEFT WITH THE APPLIANCE All manuals and user guides at all guides com a l l g u i d e s c o m ...

Page 2: ...as not fulfilled his obligations to record the information required by the initiative It is important that The services and the system are properly flushed as specified The User is clearly instructed on the correct operation of the appliance The benefits of regular servicing are explained to maintain the efficiency and extend the life of the appliance 2 1 These instructions cover both conventional...

Page 3: ...r circumstances Central Heating and Hot Water Mode The appliance will supply heat to the central heating system as required The water supplied to the central heating circuit can be set to the desired temperature by adjusting the heating control thermostat located on the facia panel SPECIFICATIONS Model 12 14 15 19 20 25 POWER SUPPLY 230V 50 Hz 230V 50 Hz 230V 50 Hz IP RATING IP 20 IP20 IP 20 HEATI...

Page 4: ... kW Btu hr kW Btu hr Output Kg h l h 28 Sec Kerosene 0 50 60 ES 110 1 40 1 77 215 10 5 8 5 17 58 000 15 51 000 28 Sec Kerosene 0 55 80 EH 115 1 59 2 01 225 10 5 8 75 19 65 000 17 58 000 28 Sec Kerosene 0 60 60 ES 105 1 78 2 25 235 11 5 9 0 21 5 73 000 19 65 000 35 Sec Gas Oil 0 50 80 S 155 1 80 2 12 235 11 5 9 0 21 5 73 000 19 65 000 NOMINAL BOILER RATING AT NORMAL OPERATING TEMPERATURE 15 19 Tabl...

Page 5: ...efficient combustion an adequate supply of air must be delivered to the combustion chamber To provide sufficient air a suitable inlet should be provided into the room or space in which the boiler is situated the sizes of which are given in Table 5 An air brick or other form of continuous air supply may have to be built into the installation in order to ensure an adequate supply of air 6 2 If the a...

Page 6: ...screw Pressure relief valve Central heating flow Pump Burner Front panel Expansion vessel Electrical panel User operating switch Optional programmer position Top panel Thermostat knob Fire valve clip Manual reset over heat thermostat phial Automatic reset high limit thermostat phial Control thermostat phial Split pin Control Box Assembly All manuals and user guides at all guides com a l l g u i d ...

Page 7: ...e relief valve Central heating flow Pump Burner Front panel Expansion vessel Electrical panel User operating switch Optional programmer position Top panel Thermostat knob Fire valve clip Burner cover Rear air duct Rear air duct access cover Manual reset over heat thermostat phial Automatic reset high limit thermostat phial Control thermostat phial Split pin Control Box Assembly All manuals and use...

Page 8: ...terminal arrangement 7 3 Room Sealed Balanced Flue Model RS The appliance is supplied ready for installation as a low level discharge balanced flue system by the simple addition of one of the flue terminal kit options shown in Fig 6 Details of the installation procedure are included in the Flue Terminal Installation instructions supplied with the terminal kit Alternatively a range of room sealed b...

Page 9: ...Discharge 4 to 7 Single Skin Wall For use with non standard single skin walls up to 182 mm thick Where noise emission from the flue terminal is likely to be of concern it is recommended that the standard 12 in terminal is used and the appliance stood away from the wall to take up the extra terminal body length c Rear Discharge Extension Kit 12 to 36 Wall X For use where the wall thickness exceeds ...

Page 10: ...nal facing the terminal Not allowed 1200 K Vertically from a terminal on the same wall Not allowed 1500 L Horizontally from a terminal on the same wall Not allowed 750 M Above an intersection with the roof 600 Not applicable 732 N From a vertical structure on the side of the terminal 750 Not applicable 750 O Above a vertical structure less than 750mm from the side of the terminal 600 Not applicabl...

Page 11: ...b The oil supply pipe should be laid as level as possible to avoid air pockets and unnecessary friction losses c The following components should be fitted in the fuel line between the storage tank and burner 1 A manual isolating valve installed as close to the tank as possible 2 A fire valve in accordance with BS5410 as shown in Fig 10 The fire valve should be fitted externally with a fire detecti...

Page 12: ...um Fire valve to BS 5410 Fire valve to BS 5410 Isolating valve Isolating valve Fire detection element Filter Burner Burner Wall Wall b Double pipe system Isolating valve Non return valve Non return valve Fire detection element Isolating valve Oil tank c Single pipe lift system with de aerator Fire valve to BS 5410 H 3 5 m 11 5 ft maximum Burner Wall Fire detection element De aerator H 3 5 m 11 5 f...

Page 13: ...tems when all of the radiators are fitted with thermostatic radiator valves 9 5 The pressure jet burner fitted to the appliance has full auto matic control and hence there is no requirement for heat leak radiators 9 6 Any unused boiler tappings should be plugged prior to filling 9 7 The primary system should be flushed and treated in accordance with the recommendations of BS 7593 before the system...

Page 14: ...The filling point must be at low level and must never be a permanent direct fixing to the mains water supply 9 16 Water loss must be replaced See Fig 13 The connection should be made to the central heating return as close to the appliance as possible 9 17 The make up vessel where fitted must be fitted with a non return valve 9 18 Repeated venting loses water from the system It is essential that th...

Page 15: ...16a A plug in colour co ordinated 2 channel electronic programmer is available from Worcester Heat Systems Limited Full instructions covering installation and operation of the programmer are included with the kit The programmer will give fully independent central heating CH and hot water HW programmes when the switch on the rear of the unit is set to P If an external programmer is to be fitted to ...

Page 16: ...ations having pumped circulation to both the domestic hot water and radiator circuits The domestic hot water and radiator circuits are independently controlled by two motorised valves via a cylinder thermostat and a room thermostat Both thermostats switch the water circulator and the boiler on and off 10 9 Honeywell Y Plan See Fig 19 The Y Plan provides complete control on installations having pum...

Page 17: ... 1 to 3 and link 2 to 4 and make link 3 to 4 10 WAY JUNCTION BOX NOTE If a frost thermostat is required it can be wired to the remote junction box NOTE The 10 way junction box must be a terminal block type and current rated to at least 5 amps Remote Pre wired Junction Box OUTSIDE BOILER INSIDE BOILER 7 8 910 X External Pump disconnect and remove Pump supplied in boiler NOTE Optional Worcester Prog...

Page 18: ...ve link 1 to 3 and link 2 to 4 and make link 3 to 4 Grey White Blue Brown Room thermostat Pump supplied in boiler N E NL HEAT SYSTEMS HEATING ADVANCE OFF TWICE ONCE ON OFF TWICE ONCE ON SELECT LOCK SET YES SELECT PM TUE HOT WATER ADVANCE Burner Socket Optional Worcester Programmer Cylinder Thermostat C 1 2 Mid Position Valve Honeywell V4073A E N L N E E N 1 2 3 4 5 6 7 8 9 1112131415 10 Blue Brown...

Page 19: ...ith the open grommet supplied in the plastic bag 4 Slacken the pipe retaining clip screw located directly below the grommet hole When using 12mm copper pipe replace the clip with the larger one supplied 5 Bend a piece of 10mm or 12mm copper tube as selected to the correct profile to allow the pipe to be fed down the side of the appli ance Make a slight chamfer on the end of the pipe to be fed thro...

Page 20: ... using a 5mm Allen key Note It is important that a good seal is made between the burner and the boiler to prevent re circulation of the flue gases from the combustion chamber to the burner inlet or the room in the case of a CF LLD appliance 3 On the RS balanced flue model feed the electrical lead back through the hole in the burner surround housing and fit the grom met into the hole ensuring a sea...

Page 21: ...e correctly located If the baffles are correctly located then reduce the pump pressure since nozzle variations of up to or 15 may occur 12 15 Remove the oil pressure gauge and manifold and check all oil system joints for any signs of leakage 12 16 On the RS balanced flue model fit the burner cover box supplied in the flue terminal kit by lining up the four ball studs and the polarising pin in the ...

Page 22: ... nozzle line and rotate the adjusting disc one turn anti clockwise to move forward by 1 mm Output Dimension kW Head Type A 15 PL 6 7 21 5 10 3 mm 17 PL 6 7 21 5 10 5 mm 19 PL 6 7 21 5 10 5 mm Fig 22 Electro Oil Inter B11 Burner 20 25 model Combustion Head Air control indicator Photocell Air adjustment screw 4 mm hexagonal head Transformer Control box Oil pump Pressure adjustment screw Draught tube...

Page 23: ... 2 Pre Service Check 1 Remove the cabinet front and top panels as described in Section 5 2 On the RS balanced flue model remove the burner cover box as described in Section 5 5 3 Operate the appliance and system noting any faults which may need to be corrected during the service 14 3 Cleaning the Burner IMPORTANT Disconnect the electrical supply at the mains before commencing any servicing Turn of...

Page 24: ...e of a CF LLD appliance 14 4 Remove the paper element from the external oil filter and replace If the filter contains a washable element then thoroughly clean in Kerosene or white spirit and re assemble into the filter 14 5 Clean the air ducts RS balanced flue model only 1 Remove the rear duct top cover 2 Shine a light down the rear duct and inspect both the rear and under duct for any sign of deb...

Page 25: ...ogrammer open circuit Check by linking 8 and 9 on the connector Faulty control box Replace if necessary Flue draught incorrect Check flue draught Combustion settings incorrect Set up as in installation instructions Faulty nozzle Replace nozzle HIGH SMOKE NUMBER Faulty nozzle Replace nozzle Incorrect combustion settings Readjust as in installation instructions Oil pressure incorrect Adjust to recom...

Page 26: ...ox Base Satronic S01 S701 1 8 716 142 782 0 Ignition Electrode 1 8 716 142 752 0 Motor B9 AEG or Simel 70 W 1 8 716 156 597 0 Motor B11 AEG FHP 90W 1 8 716 142 732 0 Oil Pump B9 Danfoss BFP41L3 1 8 716 142 743 0 Oil Pump B11 Danfoss BFP11L3 1 8 716 142 736 0 Transformer Danfoss EBI 052F0030 excludes cable 1 8 716 156 696 0 Mechanical Shut Off Valve 1 8 716 156 658 0 Flexible Oil Line Kit WHS 1 8 7...

Page 27: ...27 All manuals and user guides at all guides com ...

Page 28: ...inued improvement All goods sold are subject to our official Conditions of Sale a copy of which may be obtained on application 8 716 114 733a 11 07 Worcester Heat Systems Limited Bosch Group Cotswold Way Warndon Worcester WR4 9SW Telephone 01905 754624 Fax 01905 754619 Technical Helpline 08705 266241 www worcester bosch co uk All manuals and user guides at all guides com ...

Reviews: