background image

(c) 

Clean  both  sides  of  the  fan  impeller  and  remove  any  debris

from the burner housing.
(d) Check that the impeller rotates freely.

(e) 

Clean  the  air  inlet  passage  and  check  that  the  adjustment

mechanism operates freely.

(f) 

Re-assemble the components.

Electro Oil Inter B11
(a) 

Remove the acoustic fan inlet cover.

(b) 

Remove the three screws holding the fan cowl in position and

remove the cowl noting how the fan control flap is positioned.

(c) 

Check that the air control flap pivots freely and ensure the air

path to the burner head is clear.

(d) 

Clean both sides of the fan impeller and remove any debris

from the burner housing.

(e) 

Check that the impeller rotates freely.

( f )

Re-assemble the components.

3. 

Remove the combustion head and thoroughly clean all deposits.

4. Inspection of Mechanical Shut-off Valve.
(a) 

Remove the nozzle.

(b) 

Fasten an M5 screw, with a minimum length of 30mm, into

the threaded hole (A) and pull the screw to withdraw the check
valve.

(c)

Check that the nozzle holder is clear of any debris and clean if

necessary.

(d)

Check that the three holes in the check valve are clear of any

debris. Discard the check valve if the holes cannot be cleared or
if the unit is defective and replace with a new one.

(e)

Replace in the reverse order.

5. 

It  is  strongly  recommended  that  the  oil  atomising  nozzle  is

replaced at each service. If this is not possible then remove and
clean the integral filter, but under no circumstances should the
nozzle be stripped into its component parts and never attempt
to clean the nozzle tip.

6. 

Check and reset the electrodes, where necessary, as shown in

Figs. 20, 21 and 22.

7. 

Replace the combustion head and check that the nozzle lies

central  to  the  combustion  head  and  the  head  settings  are  as
shown in Figs. 20, 21 and 22.

8. 

Withdraw the photocell from its housing and clean.

9. 

Remove and clean the oil pump internal filter using kerosene

or white spirit. The internal filter is accessed by removing the oil
pump  cover  on  the  Danfoss  BFP  11  and  Suntec  AS47C  and  by
unscrewing  and  withdrawing  the  cartridge  on  the  Danfoss  BFP
41 as indicated in Fig. 9 

10. 

It  is  recommended  that  the  standard  flexible  oil  line  is

replaced  at  each  yearly  service  to  prevent  the  possibility  of  a
leak due to ageing.

11. 

Re-assemble the burner components.

12. 

Check  the  sponge  O-ring  seal  located  around  the  combus-

tion head and replace if necessary. It is imperative that this seal
is in good condition since failure will cause the flue gases to be
re-circulated  into  the  burner  inlet,  or  the  room  in  the  case  of  a
CF/LLD appliance.

14.4 

Remove  the  paper  element  from  the  external  oil  filter  and

replace. If the filter contains a washable element then thoroughly

clean in Kerosene or white spirit and re-assemble into the filter.

14.5 Clean the air ducts. 

(RS balanced flue model only).

1. 

Remove the rear duct top cover 

2. 

Shine a light down the rear duct and inspect both the rear and

under duct for any sign of debris and clean where necessary using
a  flexible  hose  connected  to  a  vacuum  cleaner.  A  short  length  of
garden hose would be suitable for this purpose. 

3. 

Replace the rear duct top cover.

4. 

Check that the oil bleed holes are clear. These are located in the

base  of  the  burner  cover  box  and  the  bottom  front  face  of  the
burner housing.

14.6 Clean the Boiler.
1. 

Remove  the  boiler  top  access  door  by  releasing  the  two  M10

nuts  and  check  the  fibreglass  rope  seal.  Replace  the  seal  if
necessary.

2. 

Remove and check the baffle retainer where fitted (20-25 model

only). (See Fig. 23c).

3. 

Remove  the  baffles  and  clean  and  check  their  condition.

Replace any baffles considered to be badly corroded.

4. 

Thoroughly clean all of the heat exchanger surfaces using a stiff

wire brush and vacuum clean all loose debris from the combustion
chamber. Take care not to damage the base installation.

5. 

Remove  and  check  the  heat  shield  where  fitted  (20-25  model

only). (See Fig. 23c).

6. 

Check  the  combustion  chamber  base  insulation  board  and

replace if there is any sign of damage.

7. 

Check and clean the flue system if necessary.

8. 

Replace  the  items  in  reverse  order  noting  the  baffle  positions

shown in Fig. 23.

14.7 Re-commission the Burner.
1. 

Connect the flexible oil supply hose to the isolating valve bulk-

head fitting and tighten sufficiently to form a good seal. Where a
double  pipe  system  is  being  used  connect  the  oil  return  flexible
hose to return pipe fitting.

2. 

With  the  sponge  O-ring  gasket  around  the  burner  blast  tube

insert the burner into the housing tube. Push the burner firmly for-
ward to compress the gasket and tighten the two locking screws
using a 5mm Allen key.

Note: 

It is important that a good seal is made between the burner

and the boiler to prevent re-circulation of the flue gases from the
combustion chamber to the burner inlet, or the room in the case of
a CF/LLD appliance.

3. 

On  the  RS  balanced  flue  model  feed  the  electrical  lead  back

through the hole in the burner surround housing and fit the grom-
met into the hole ensuring a seal is made.

4. 

Reconnect the electrical lead plug into the control box.

5. 

Turn on the oil supply at the service cock.

6. 

Re-commission the burner as described in Section 12.

24

Check Valve

Nozzle Assembly

A

Fig. 24. Mechanical Shut-off Valve

All manuals and user guides at all-guides.com

Summary of Contents for Worcester Danesmoor 12/14

Page 1: ...ater and Central Heating 12 14 MINIMUM 12 kW 41 000 Btu h MAXIMUM 14 kW 48 000 Btu h 15 19 MINIMUM 15 kW 51 000 Btu h MAXIMUM 19 kW 65 000 Btu h 20 25 MINIMUM 20 kW 68 000 Btu h MAXIMUM 25 kW 85 000 Btu h THESE INSTRUCTIONS APPLY TO UK MODELS ONLY THESE INSTRUCTIONS ARE TO BE LEFT WITH THE APPLIANCE All manuals and user guides at all guides com a l l g u i d e s c o m ...

Page 2: ...as not fulfilled his obligations to record the information required by the initiative It is important that The services and the system are properly flushed as specified The User is clearly instructed on the correct operation of the appliance The benefits of regular servicing are explained to maintain the efficiency and extend the life of the appliance 2 1 These instructions cover both conventional...

Page 3: ...r circumstances Central Heating and Hot Water Mode The appliance will supply heat to the central heating system as required The water supplied to the central heating circuit can be set to the desired temperature by adjusting the heating control thermostat located on the facia panel SPECIFICATIONS Model 12 14 15 19 20 25 POWER SUPPLY 230V 50 Hz 230V 50 Hz 230V 50 Hz IP RATING IP 20 IP20 IP 20 HEATI...

Page 4: ... kW Btu hr kW Btu hr Output Kg h l h 28 Sec Kerosene 0 50 60 ES 110 1 40 1 77 215 10 5 8 5 17 58 000 15 51 000 28 Sec Kerosene 0 55 80 EH 115 1 59 2 01 225 10 5 8 75 19 65 000 17 58 000 28 Sec Kerosene 0 60 60 ES 105 1 78 2 25 235 11 5 9 0 21 5 73 000 19 65 000 35 Sec Gas Oil 0 50 80 S 155 1 80 2 12 235 11 5 9 0 21 5 73 000 19 65 000 NOMINAL BOILER RATING AT NORMAL OPERATING TEMPERATURE 15 19 Tabl...

Page 5: ...efficient combustion an adequate supply of air must be delivered to the combustion chamber To provide sufficient air a suitable inlet should be provided into the room or space in which the boiler is situated the sizes of which are given in Table 5 An air brick or other form of continuous air supply may have to be built into the installation in order to ensure an adequate supply of air 6 2 If the a...

Page 6: ...screw Pressure relief valve Central heating flow Pump Burner Front panel Expansion vessel Electrical panel User operating switch Optional programmer position Top panel Thermostat knob Fire valve clip Manual reset over heat thermostat phial Automatic reset high limit thermostat phial Control thermostat phial Split pin Control Box Assembly All manuals and user guides at all guides com a l l g u i d ...

Page 7: ...e relief valve Central heating flow Pump Burner Front panel Expansion vessel Electrical panel User operating switch Optional programmer position Top panel Thermostat knob Fire valve clip Burner cover Rear air duct Rear air duct access cover Manual reset over heat thermostat phial Automatic reset high limit thermostat phial Control thermostat phial Split pin Control Box Assembly All manuals and use...

Page 8: ...terminal arrangement 7 3 Room Sealed Balanced Flue Model RS The appliance is supplied ready for installation as a low level discharge balanced flue system by the simple addition of one of the flue terminal kit options shown in Fig 6 Details of the installation procedure are included in the Flue Terminal Installation instructions supplied with the terminal kit Alternatively a range of room sealed b...

Page 9: ...Discharge 4 to 7 Single Skin Wall For use with non standard single skin walls up to 182 mm thick Where noise emission from the flue terminal is likely to be of concern it is recommended that the standard 12 in terminal is used and the appliance stood away from the wall to take up the extra terminal body length c Rear Discharge Extension Kit 12 to 36 Wall X For use where the wall thickness exceeds ...

Page 10: ...nal facing the terminal Not allowed 1200 K Vertically from a terminal on the same wall Not allowed 1500 L Horizontally from a terminal on the same wall Not allowed 750 M Above an intersection with the roof 600 Not applicable 732 N From a vertical structure on the side of the terminal 750 Not applicable 750 O Above a vertical structure less than 750mm from the side of the terminal 600 Not applicabl...

Page 11: ...b The oil supply pipe should be laid as level as possible to avoid air pockets and unnecessary friction losses c The following components should be fitted in the fuel line between the storage tank and burner 1 A manual isolating valve installed as close to the tank as possible 2 A fire valve in accordance with BS5410 as shown in Fig 10 The fire valve should be fitted externally with a fire detecti...

Page 12: ...um Fire valve to BS 5410 Fire valve to BS 5410 Isolating valve Isolating valve Fire detection element Filter Burner Burner Wall Wall b Double pipe system Isolating valve Non return valve Non return valve Fire detection element Isolating valve Oil tank c Single pipe lift system with de aerator Fire valve to BS 5410 H 3 5 m 11 5 ft maximum Burner Wall Fire detection element De aerator H 3 5 m 11 5 f...

Page 13: ...tems when all of the radiators are fitted with thermostatic radiator valves 9 5 The pressure jet burner fitted to the appliance has full auto matic control and hence there is no requirement for heat leak radiators 9 6 Any unused boiler tappings should be plugged prior to filling 9 7 The primary system should be flushed and treated in accordance with the recommendations of BS 7593 before the system...

Page 14: ...The filling point must be at low level and must never be a permanent direct fixing to the mains water supply 9 16 Water loss must be replaced See Fig 13 The connection should be made to the central heating return as close to the appliance as possible 9 17 The make up vessel where fitted must be fitted with a non return valve 9 18 Repeated venting loses water from the system It is essential that th...

Page 15: ...16a A plug in colour co ordinated 2 channel electronic programmer is available from Worcester Heat Systems Limited Full instructions covering installation and operation of the programmer are included with the kit The programmer will give fully independent central heating CH and hot water HW programmes when the switch on the rear of the unit is set to P If an external programmer is to be fitted to ...

Page 16: ...ations having pumped circulation to both the domestic hot water and radiator circuits The domestic hot water and radiator circuits are independently controlled by two motorised valves via a cylinder thermostat and a room thermostat Both thermostats switch the water circulator and the boiler on and off 10 9 Honeywell Y Plan See Fig 19 The Y Plan provides complete control on installations having pum...

Page 17: ... 1 to 3 and link 2 to 4 and make link 3 to 4 10 WAY JUNCTION BOX NOTE If a frost thermostat is required it can be wired to the remote junction box NOTE The 10 way junction box must be a terminal block type and current rated to at least 5 amps Remote Pre wired Junction Box OUTSIDE BOILER INSIDE BOILER 7 8 910 X External Pump disconnect and remove Pump supplied in boiler NOTE Optional Worcester Prog...

Page 18: ...ve link 1 to 3 and link 2 to 4 and make link 3 to 4 Grey White Blue Brown Room thermostat Pump supplied in boiler N E NL HEAT SYSTEMS HEATING ADVANCE OFF TWICE ONCE ON OFF TWICE ONCE ON SELECT LOCK SET YES SELECT PM TUE HOT WATER ADVANCE Burner Socket Optional Worcester Programmer Cylinder Thermostat C 1 2 Mid Position Valve Honeywell V4073A E N L N E E N 1 2 3 4 5 6 7 8 9 1112131415 10 Blue Brown...

Page 19: ...ith the open grommet supplied in the plastic bag 4 Slacken the pipe retaining clip screw located directly below the grommet hole When using 12mm copper pipe replace the clip with the larger one supplied 5 Bend a piece of 10mm or 12mm copper tube as selected to the correct profile to allow the pipe to be fed down the side of the appli ance Make a slight chamfer on the end of the pipe to be fed thro...

Page 20: ... using a 5mm Allen key Note It is important that a good seal is made between the burner and the boiler to prevent re circulation of the flue gases from the combustion chamber to the burner inlet or the room in the case of a CF LLD appliance 3 On the RS balanced flue model feed the electrical lead back through the hole in the burner surround housing and fit the grom met into the hole ensuring a sea...

Page 21: ...e correctly located If the baffles are correctly located then reduce the pump pressure since nozzle variations of up to or 15 may occur 12 15 Remove the oil pressure gauge and manifold and check all oil system joints for any signs of leakage 12 16 On the RS balanced flue model fit the burner cover box supplied in the flue terminal kit by lining up the four ball studs and the polarising pin in the ...

Page 22: ... nozzle line and rotate the adjusting disc one turn anti clockwise to move forward by 1 mm Output Dimension kW Head Type A 15 PL 6 7 21 5 10 3 mm 17 PL 6 7 21 5 10 5 mm 19 PL 6 7 21 5 10 5 mm Fig 22 Electro Oil Inter B11 Burner 20 25 model Combustion Head Air control indicator Photocell Air adjustment screw 4 mm hexagonal head Transformer Control box Oil pump Pressure adjustment screw Draught tube...

Page 23: ... 2 Pre Service Check 1 Remove the cabinet front and top panels as described in Section 5 2 On the RS balanced flue model remove the burner cover box as described in Section 5 5 3 Operate the appliance and system noting any faults which may need to be corrected during the service 14 3 Cleaning the Burner IMPORTANT Disconnect the electrical supply at the mains before commencing any servicing Turn of...

Page 24: ...e of a CF LLD appliance 14 4 Remove the paper element from the external oil filter and replace If the filter contains a washable element then thoroughly clean in Kerosene or white spirit and re assemble into the filter 14 5 Clean the air ducts RS balanced flue model only 1 Remove the rear duct top cover 2 Shine a light down the rear duct and inspect both the rear and under duct for any sign of deb...

Page 25: ...ogrammer open circuit Check by linking 8 and 9 on the connector Faulty control box Replace if necessary Flue draught incorrect Check flue draught Combustion settings incorrect Set up as in installation instructions Faulty nozzle Replace nozzle HIGH SMOKE NUMBER Faulty nozzle Replace nozzle Incorrect combustion settings Readjust as in installation instructions Oil pressure incorrect Adjust to recom...

Page 26: ...ox Base Satronic S01 S701 1 8 716 142 782 0 Ignition Electrode 1 8 716 142 752 0 Motor B9 AEG or Simel 70 W 1 8 716 156 597 0 Motor B11 AEG FHP 90W 1 8 716 142 732 0 Oil Pump B9 Danfoss BFP41L3 1 8 716 142 743 0 Oil Pump B11 Danfoss BFP11L3 1 8 716 142 736 0 Transformer Danfoss EBI 052F0030 excludes cable 1 8 716 156 696 0 Mechanical Shut Off Valve 1 8 716 156 658 0 Flexible Oil Line Kit WHS 1 8 7...

Page 27: ...27 All manuals and user guides at all guides com ...

Page 28: ...inued improvement All goods sold are subject to our official Conditions of Sale a copy of which may be obtained on application 8 716 114 733a 11 07 Worcester Heat Systems Limited Bosch Group Cotswold Way Warndon Worcester WR4 9SW Telephone 01905 754624 Fax 01905 754619 Technical Helpline 08705 266241 www worcester bosch co uk All manuals and user guides at all guides com ...

Reviews: