Fitting
6720814332 (2018/04)
22
Mounting on a cascade frame
▶ For details on mounting the boiler in a cascade frame, see the
installation instructions for the cascade system.
5.4
Remove the protective caps
▶ Take the caps off the connections on the underside of the boiler.
5.5
Hydraulic and gas connections
There are 2 ways to make the hydraulic and gas connections:
• Using the pump group (accessory) (
Chapter 5.6)
• Without using the pump group (
Chapter 5.7).
5.6
Mounting the pump group (accessory)
The following components have been incorporated into the pump group:
• Gas isolation valve
• Flow and return isolation valves
• Pressure gauge
• Thermometer
• Pressure Relief Valve
• Pump
• Drain & fill valve (DFV)
Fig. 36 Pump group scope of delivery
[1]
Casing (insulation)
[2]
Back panel (insulation)
[3]
Return pipe
[4]
Flat gasket 1½ " (2 × )
[5]
Gas isolation valve
[6]
PRV and condensate T-piece
[7]
Connection piece
[8]
Flow pipe
5.6.1
Installing the gas isolation valve
▶ Seal the gas connection on the boiler using an approved sealant [1].
▶ Mount the gas isolation valve G 1" in the gas line [2].
▶ Connect the gas pipe without stress to the gas isolation valve.
Fig. 37 Installing the gas isolation valve
[1]
Sealing agents
[2]
Gas isolation valve
5.6.2
Mounting the pump group
▶ Attach the screw fitting delivered with the boiler (
the flow and return connection of the boiler.
▶ Connect the pump group to the flow and return connection of the
boiler.
▶ Use the flat gaskets [1] (included in the scope of delivery) for this.
NOTICE:
Water damage.
The boiler may contain water. This can be discharged
when the caps are removed.
▶ Keep a bucket and cloth handy.
NOTICE:
Installation damage.
The pump group includes a pressure relief valve.
▶ Check whether the excess pressure, the operating
pressure and components in the heating system
suite each other.
▶ If necessary, replace the PRV with a PRV of
appropriate excess pressure. Maximum boiler
pressure is 4 bar.
6 720 807 034-028.1DDC
2
3
4
5
8
1
7
6
Avoid damage to the gas valve with older gas lines.
▶ Install a gas filter in the gas line.
6 720 807 034-06.1DDC
2