Display codes
6720814332 (2018/04)
45
9 A
3 6 1
3
The burner control unit that has been fitted is not
compatible with the KIM.
▶ Check the numbers on the burner control unit.
▶ Fit a KIM with the correct KIM number.
9 U
2 3 3
3
The burner control unit or the KIM is faulty.
▶ Check plug and wiring of the burner control unit.
▶ Check the operating characteristics of the boiler by replacing the
burner control unit.
A 3
3 1 7
3
Short circuit in the flue gas temperature sensor
contacts.
▶ Check the function of the flue gas temperature sensor by replacing
the component.
b 7
2 5 7
3
The burner control unit or the KIM is faulty.
▶ Check plug and wiring of the burner control unit.
▶ Check the operating characteristics of the boiler by replacing the
burner control unit.
C 1
2 6 4
2
No control signal or power supply to the fan during
operation.
▶ Check plug and cabling of the fan.
▶ Check the function of the fan, replace the component if necessary.
C 4
2 7 3
2
The boiler was switched off for a maximum of
2 minutes because it had been operating
continuously for more than 24 hours. This is a
safety check.
C 6
2 1 5
3
The fan speed is too high.
▶ Check plug and cabling of the fan.
▶ Check the operating characteristics of the boiler by replacing the fan.
▶ Check the plug of the burner control unit.
▶ Check the operating characteristics of the boiler by replacing the
burner control unit.
C 6
2 1 6
3
The fan speed is too low.
C 7
2 1 4
3
The fan does not run during the start phase (
- -
).
C 7
2 1 7
3
The fan speed is irregular when starting up.
C E
2 0 7
2
Water pressure is too low.
▶ Top up heating system with water until a pressure of 2 bar is
reached.
▶ Check the expansion vessel.
▶ Check the heating system for leaks.
▶ Check the wiring and function of the pressure sensor.
C E
2 6 6
3
Pump test failed.
▶ Check the water pressure of the boiler, vent the heating system and
the boiler.
▶ Check whether it is possible to achieve sufficient flow in the heating
system.
▶ Check function of the pump.
▶ Check function and cabling of the pressure sensor.
▶ Check the operating characteristics of the boiler by replacing the
faulty component.
d 1
2 4 0
3
The contacts of the boiler return temperature
sensor have short-circuited.
▶ Check the water pressure of the boiler, vent the heating system and
the boiler.
▶ Check whether it is possible to achieve sufficient flow in the heating
system.
▶ Check plug and cabling of the boiler return temperature sensor.
▶ Check the function of the boiler by replacing the boiler return
temperature sensor.
d 1
2 4 1
3
The contacts of the boiler return temperature
sensor have been interrupted.
d 3
2 3 2
The external switching contact has opened.
▶ Check the jumper at the connection of the external switching
contact.
▶ Check the external switching contact.
d 4
2 1 3
The actual temperature recorded by the flow
temperature sensor or return temperature sensor
is rising too quickly.
▶ Check the water pressure of the boiler, vent the heating system and
the boiler.
▶ Check whether it is possible to achieve sufficient flow in the heating
system.
▶ Check the cabling to the pump and corresponding sensors.
Replace the faulty component if necessary.
d 4
2 7 1
2
Actual temperature differential between flow and
safety temperature sensor is too high.
▶ Check the water pressure of the boiler, vent the heating system and
the boiler.
▶ Check whether it is possible to achieve sufficient flow in the heating
system.
▶ Check the operating characteristics and cabling of the pump and
corresponding sensor. Replace the faulty component if necessary.
Code
Code
type Designation
Remedy
Table 19 Operating and fault codes