Commissioning
6 720 808 928 (2017/06)
36
Confirming or rejecting the change
6.7.2
Central heating settings - Outdoor temperature or Room
temperature compensated control
The pump operation when used with a HIU unit does not need to be
optimised and the
Pump economy mode
should be disabled.
▶ Enter the
Service menu
and navigate through the menus and select
the
Heating settings
menu.
▶ Navigate through the
Heating settings
and select
Heating circuit 1
▶ Set
Pump economy mode
to
No
.
Outdoor temperature or Room temperature compensated control
Compensated control modulates the central heating flow temperature
via the central heating pump and control valve position to control the
required flow of heated water into the system.
The default central heating room temperature control is
Weather-
compensated
but can be set to
Room temperature-dependent
.
▶ Enter the
Service menu
and navigate through the menus and select
the
Heating settings
menu.
▶ Navigate through the
Heating settings
and select
Heating circuit 1
.
▶ Navigate through the
Heating circuit 1
and select
Control type
.
▶ Set
Control type
to
Room temperature-dependent
.
6.7.3
Heat Interface Unit settings
▶ Enter the
Service menu
and navigate through the menus and select
the
Heat Interface Unit settings
menu.
▶ Navigate through the
Heat Interface Unit settings
and select the
parameter required.
▶ Adjust the parameter as required.
6.7.4
Electronic by-pass function setup
DHW circulation for electronic by-pass function
Check that the
DHW circulation pump
is enabled.
▶ Enter the
Service menu
and navigate through the menus and select
the
DHW settings
menu.
▶ Navigate through the
DHW settings
and select
DHW system I
menu.
▶ Navigate through the
DHW system I
and select
DHW circulation
pump
.
▶ Ensure that the
DHW circulation pump
is set to
On
.
Following checking
DHW circulation pump
is enabled you will need to
set the
DHW circ.pmp op.mode
.
▶ Navigate through the
DHW system I
and select
DHW circ.pmp
op.mode
.
▶ Set
DHW circ.pmp op.mode
to
On
.
Rejecting the change
&
▶ Press the selector to activate the marked entry or to
confirm the change.
▶ Turn the selector to highlight
Continue
and press the
selector.
The Display switches to the higher menu level. The
user interface operates with the modified setting.
Rejecting the change
▶ Press the Back key to undo the change.
Table 18
Heating circuit 1:
Parameter
Description
Pump economy mode ▶ Optimised pump operation for the heat
source.
– Yes = Enabled
– No = Disabled
Default value is Yes.
Table 19
Heating circuit 1:
Parameter
Description
Control type
▶ Central heating control method.
– Weather-compensated
– Outside temp. with base point
– Room-temperature-dependent
– Room temperature output
– Single room-dependent
Default value is Weather-compensated.
Table 20
Heat Interface Unit
settings: Parameter Description
Set return
temperature
District return temperature set point.
▶ Range from 0 - 90 ( °C)
Default value is 50 °C
Min. contr. valve off
time
Minimum CH delay time, (to avoid control
valve oscillations).
▶ Range from 0 - 60 minutes
Default value is 3 minutes.
Calibrate control valve Calibration DHW/CH control valve via
controller.
▶ Select either DHW or CH
– Off = Normal operation
– On = Calibrate valve
Once On has been selected the calibration
starts and the value returns to Off.
Table 21
DHW settings:
Parameter
Description
DHW circulation pump ▶ Control of DHW circulation pump by heat
source.
– Off = Disabled
– On = Enabled
Default value is On.
Table 22
DHW settings:
Parameter
Description
DHW circ.pmp
op.mode
▶ Operating mode for the DHW circulation
pump.
– Off = Disabled
– On = Enabled
– As DHW system I = As per timings for
DHW demand
– Own time program = Separate time
control
Default value is Off.