2. SETTING PARAMETERS
The Differential Pressure is factory set to 0.4 Bar. To reset the parameters (for example,
the pressure differential) the following sequence needs to be followed on the VEXO
®
iX-1 Controller. See list of parameters on previous page:
•
Press and hold “Set” button 4 to access parameters
•
Enter code “815” and then while holding set press the up or down button to access
required parameter.
•
Change the parameter setting using up or down
•
Press and hold set to save required setting, the controller will scroll “Saving” and
return to main screen.
•
3. FAULT MESSAGES
If a fault is detected, the VEXO
®
iX-1 Controller display will scroll a Fault Message as below.
The VEXO
®
iX-1 Controller will also initiate the visual strobe and sounder to draw attention
to the user.
FAULT
MESSAGE
X-POT6+
Operation
Solution
Blocked Filter Shutdown
Isolate the X-POT6+ and Clean/Change Filters to allow
X-POT6+ to operate
Sensor 1
Fail
Shutdown
Call Engineer to check connections and replacement of
the Pressure Transducer
Sensor 2
Fail
Shutdown
Call Engineer to check connections and replacement of
the Pressure Transducer
Pump Fail
Shutdown
Call Engineer to check connections and replacement of
the Pump
The VEXO
®
iX-1 Controller if connected to a BMS, it will send a “Common Fault” signal to
draw attention to the user.