FILteR mAIntenAnCe (ContInued)
2. To Clean and Replace the Filters
1.
The operative must wear protective gloves and eyewear for this operation.
2.
Use of the main BOSS™ X-POT6+ Schematic (Page 10) is required to follow the main
part numbers.
3.
Turn the power off to the BOSS™ X-POT6+ unit by turning the Mains ON/OFF Power
Switch (22) through 90
o
.
4.
Check to see the power is off, the power to the VEXO
®
iX-1 Controller (21). The screen
should be blank and off and the pump will not run.
5.
Manually close the 1” Isolating Valves (1 & 3) on the Dirty Flow into the BOSS™
X-POT6+
.
6.
Manually close the 1” Isolating Valves (8 & 11) on the Clean Return from the BOSS™
X-POT6+.
7.
Manually open the 1” Isolating Valve (12). This will open the BOSS™ X-POT6+ Vessel
(4) to drain.
8.
Remove the
½
” plug and manually open the
½
” Manual Vent Isolating Valve (19). This
will open the BOSS™ X-POT6+ Vessel (4) to atmosphere and will help the BOSS™
X-POT6+ Vessel (4) drain quicker.
NOTE: If the system water is hot, leave enough time for the water to cool sufficiently
before working on this vessel.
9.
Un-tie and remove the top insulation cover and store in a clean and dry place.
10.
Once you are content that all of the liquid within the vessel has been drained out;
11.
Carefully loosen the 8off nuts which hold the lid in place. Please ensure the nuts
are loosen in an opposite order, for example, front then back, then left to right and
diagonals etc.
12.
Once all of the nuts have been loosened sufficiently, undo the nut to the end of the
bolt and swing the arms of the bolts down to the side of the Vessel.
13.
The lid of the vessel can now be carefully removed and placed on a clean dry surface.
14.
Remove the 6 Magnet Grate (5) by the handle and place the Magnet Grate (5) onto
a flat surface so the grate can be worked on
.
15.
Remove the Baffle Plate (6) by the lifting ring and place it onto a flat surface for
cleaning.
16.
Remove the dirty Cartridge Filter (7) and dispose of in an approved manner.
17.
Replace the Cartridge Filter (7) with an approved new clean Cartridge Filter (7) and
lower it into the Vessel Body (4) ensuring the spigot at the bottom of the Cartridge
Filter (7) seats into the bottom connection out of Vessel Body (4).
18.
Clean the Baffle Plate (6) with a clean damp cloth and then place it into the Vessel
Body (4). Ensure the 4off pins on the underside of the Baffle Plate locate into the 4off
holes in the top of the new Cartridge Filter (7), press down gently to lock the Baffle
Plate (6) into the Cartridge Filter (7).