Dari-Kool III-120 Instructions 

 1E-138B

Figure 1.  Dari-Kool III-120 Plumbing                                                       l138_1 

Figure 2.  Pressure/Temperature Relief Valve Installation 

Important  Note:  A  temperature  and  pressure  relief  valve  is  for 

protection against both excessive temperature and pressure; and 

if either of these conditions develop in the system, the valve will 

open and discharge water. ( label P/N 4016124)

4.  The optional water valve limits the water temperature when 

refrigerant heat input is too high.  It should be installed to bleed 

water to the drain or to a suitable alternate point of usage such 

as a heat exchanger or reservoir.  This normally-open valve is 

closed only when energized, so it will be open when the water 

in the Dari-Kool III-120 reaches the thermostatic set point.  It 

will also be open if a power outage occurs.  Considerations 

should be made to accommodate a flow rate of 40 gallons 

(151 L) per hour.  See Figure 3 for the preferred installation.  

See the electrical section for wiring instructions.

5.  To fill the Dari-Kool III-120:  Close the drain valve and open a 

hot water tap to bleed the air from the tank as it fills.  Open 

the inlet water valve.  Allow sufficient time for the tank to fill, 

as indicated by a steady flow of water, then close the water 

tap and check for leaks.

6.   If  the  solenoid  water  valve  is  used,  power  will  have  to  be 

applied to the valve in order to close it while checking  

for leaks.  DO NOT apply power to the heating element unless 

it is covered with water.

7.   The Dari-Kool III-120 has dual magnesium anode protection.  

Under  certain  water  conditions,  an  offensive  odor  may  be 

noticed after the system is in operation.  To eliminate this odor, 

remove the magnesium anodes and install aluminum anodes 

(Part No. 4016425).

—  Note ———————————————————————

ALTERNATE PRESSURE/TEMPERATURE RELIEF VALVE.

In the event that the combination pressure/temperature relief valve 

is lost or damaged, an alternate device may be used providing it:

• 

has a minimum thermal rating of 100,000 BTUH (3 kW hours)

• 

has a maximum pressure rating of 150 PSIG  (1000 kPa)

• 

is certified as meeting the requirements of ANSI Z231.22, by a 

nationally recognized testing laboratory.

4.

 Installing the Refrigeration System

4.1 

Installation Layout

The  Dari-Kool  III-120  is  designed  for  use  in  refrigeration 

systems  that  have  adequately-sized  air-or  water-cooled 

condensors.    The  Dari-Kool  III-120  should  be  installed 

between the compressor and condensor.  A number of possible 

combinations are shown in Figures 6-12.

—  Note ———————————————————————

Capillary tube systems are not normally recommended for use 

with Dari-Kool.  For special considerations, please contact the 

factory.

4.2

 Refrigerant

The  Dari-Kool  III-120  desuperheater  plate  is  designed  for 

low pressure drop.  Each of the two sections of the plate will 

handle up to 7.5 tons (26 kW) of R-22, R-404, R-407, or 5 

tons (17.5 kW) of R-134A.

Summary of Contents for Dari-Kool III-120

Page 1: ...em Disclaimers No warranties are contained in these instructions The division of responsibilities stated above is a general reminder of those provisions in the applicable dealer contract and does not...

Page 2: ...idelines must be observed 1 The Dari Kool III 120 should be in a clean dry place as close as possible to the compressor to minimize the refrigerant line lengths 2 It should be located with adequate cl...

Page 3: ...power will have to be applied to the valve in order to close it while checking for leaks DO NOT apply power to the heating element unless it is covered with water 7 The Dari Kool III 120 has dual mag...

Page 4: ...and condensor and to drop down from the compressor discharge to form a 6 152 mm trap to prevent oil and liquid refrigerant from accumulating on the discharge valve plate When two circuits of the Dari...

Page 5: ...t used control wires for valve must be isolated The equipment ground must be completed The wiring must conform to local and state electrical codes and must be installed by qualified personnel The diag...

Page 6: ...efrigerant capacity Condensing unit not to exceed 15 tons 53 kW of R 22 R 404 or R 407 or 7 5 tons 26 kW of R 134A Refer to table for recommended line sizing Figure 6 1 ton 3 5 kW of refrigerant capac...

Page 7: ...condensing unit capacity of 1 ton each Figure 9 Dari Kool III 120 in parallel with a large condensing unit Add additional Dari Kool III 120 as required Condensing unit is not to exceed 30 105 kW tons...

Page 8: ...d 15 tons 52 7 kW of R 22 R 404 or R 407 or 7 5 tons 26 kW tons of R 134A Minimum of 3 ton 10 5 kW condensing unit Figure 10 Dual condensing units dual temperature Each condensing unit does not to exc...