Dari-Kool III-120 Instructions
Figure 11. Dari-Kool III-120 in series for two temperatures with single condensing unit. Condensing unit is not to exceed 15 tons (52.7 kW) of R-22,
R-404 or R-407; or 7.5 tons (26 kW) tons of R-134A. Minimum of 3 ton (10.5 kW) condensing unit.
Figure 10. Dual condensing units
dual temperature. Each condensing unit does not to exceed 7.5 tons (26 kW) of R-22, R-404 or R-407;
or 5 tons (17.5 kW) of R-134A.
Figure 12. Insulated storage barrel installation. Refer to Figure 6 for refrigerant piping.