Manual Current relay print JGA2011
Boutronic B.V.
Boutronic B.V.
Page - 6 -
’
s-Gravenzande The Netherlands
Change settings
The settings of the JGA2011 can be changed in two ways:
With the potentiometer, the DIP-switches and the programming button or with the USB port of the
PC in combination with the Boutronic USB dongle.
Potentiometer
The switching threshold of the relay is set with the potentiometer. Each relay has its own
potentiometer. When DIP-switch 3 is OFF, the setting through the potentiometer is active.
DIP-switches
A 4-fold DIP-switch is available on the JGA2011. The following functions can be enabled or disabled
by means of the DIP-switches:
DIP Off
On
1
Reserved
Reserved
2
Reserved
Reserved
3
Use potentiometer for threshold level.
Delay is fixed 1 seconds and the
hysteresis is fixed 1%
Use software settings for threshold level,
Delay and hysteresis
4
Reserved
Reserved
Setting with the serial menu
You can change the settings with the USB port and the Boutronic Studio. The Boutronic Studio can be
downloaded from our website:
www.boutronic.nl/producten/boutronic_studio_instellen_via_windows
To connect the JGA2011 to the PC follow the next steps:
1.
Connect the JGA2011 to your PC by a Boutronic USB dongle
2.
Open the Boutronic Studio 2 with the tab ‘Terminal’, set the baud rate to 9600 and c
onnect
3.
Click on the black screen with the mouse and press three times the + (
+++)
The following text is given on the screen:
--- MENU ---
1. Relay 1
2. Relay 2
D. Debuglevel
9. Factory defaults
T. Factory test
With the ‘1, 2, D, 9 and T’ the option
will be selected
With the ‘
+
’ key the output level will be increased
With the ‘
-
’ key the output level will be decreased
With the ‘
enter
’
key the value will be stored.
With the ‘
esc
’
key the programming will be stopped.
With the ‘
9
’ key you will set all
setting to factory levels