background image

Manual Current relay print JGA2011 

 

Boutronic B.V. 

Boutronic B.V. 

Page - 6 - 

 

s-Gravenzande The Netherlands 

Change settings

 

The settings of the JGA2011 can be changed in two ways: 
With the potentiometer, the DIP-switches and the programming button or with the USB port of the 
PC in combination with the Boutronic USB dongle. 

Potentiometer

 

The switching threshold of the relay is set with the potentiometer. Each relay has its own 
potentiometer. When DIP-switch 3 is OFF, the setting through the potentiometer is active. 
 

DIP-switches

 

A 4-fold DIP-switch is available on the JGA2011. The following functions can be enabled or disabled 
by means of the DIP-switches: 
 

DIP  Off 

On 

Reserved 

Reserved 

Reserved 

Reserved 

Use potentiometer for threshold level. 
Delay is fixed 1 seconds and the 
hysteresis is fixed 1% 

Use software settings for threshold level, 
Delay and hysteresis 

Reserved 

Reserved 

Setting with the serial menu

 

You can change the settings with the USB port and the Boutronic Studio. The Boutronic Studio can be 
downloaded from our website: 

www.boutronic.nl/producten/boutronic_studio_instellen_via_windows

 

 
To connect the JGA2011 to the PC follow the next steps: 
 

1.

 

Connect the JGA2011 to your PC by a Boutronic USB dongle 

2.

 

Open the Boutronic Studio 2 with the tab ‘Terminal’, set the baud rate to 9600 and c

onnect 

3.

 

Click on the black screen with the mouse and press three times the + (

+++)

 

 

The following text is given on the screen: 
--- MENU --- 
1. Relay 1 
2. Relay 2 
D. Debuglevel 
9. Factory defaults 
T. Factory test 

 

With the ‘1, 2, D, 9 and T’ the option 

will be selected 

With the ‘

+

’ key the output level will be increased

 

With the ‘

-

’ key the output level will be decreased

 

With the ‘

enter

 key the value will be stored. 

With the ‘

esc

 key the programming will be stopped. 

With the ‘

9

’ key you will set all 

setting to factory levels 

 

 

Summary of Contents for JGA2011

Page 1: ...y JGA2011 is checked before sending for correct operation Therefore Boutronic has a warranty period of 1 year The warranty expires if The defect is caused by gross negligence or by improper installati...

Page 2: ...ns 3 Connection example 4 Operation 4 Current inputs 4 Potentiometer 5 Relay 5 Switching delay Relay 5 Change settings 6 Potentiometer 6 DIP switches 6 Setting with the serial menu 6 Relay 1 7 Relay 2...

Page 3: ...Relay1 24VD C IN 24VD C OU T www boutronic nl Made in the Netherlands Li ft front here for ac ces s control P2 Nr Unit Description 1 Connection 7 12 Connection 7 12 see front for type of connections 3...

Page 4: ...GND Level 0 100 4mA 0 20mA 100 DIP 3 OFF DIP 3 ON Software level 0 100 Delay on 1 sec Delay off 1 sec Hystereis 1 Delay on 1 600 sec Delay off 1 600 sec Hystersis 1 10 Relais 2 4 20 mA Current in 2 4...

Page 5: ...d is maximum Relay The relay switches when the corresponding input exceeds the switching threshold Input 1 switches relay 1 and input 2 switches relay 2 Switching delay Relay The switching delay with...

Page 6: ...Use software settings for threshold level Delay and hysteresis 4 Reserved Reserved Setting with the serial menu You can change the settings with the USB port and the Boutronic Studio The Boutronic St...

Page 7: ...1 sec Relay 2 Menu for changing setting relay 2 Value Description range Factory settings Level x Switching level when the relay is switching 0 100 50 Hysteresis x Hysteresis in 1 10 1 Delay on x sec...

Page 8: ...otecting range IP20 Power Description Min Typ Max Unit Remarks Power in 20 24 30 VDC 20 24 24 VAC 1 35 mA Power out 20 30 VDC 2 150 mA 3 1 Note one of the phases is directly connected to the GND 2 Thi...

Page 9: ...1 12 1 2 3 4 5 6 CONTROL Powersupply www boutronic nl GND 24VDC IN Type nummer JGA2011 24VDC OUT 4 20mA in 2 GND Inputs 4 20mA RoHS compliant TA 0 70 C Relay 1 Relay 2 4 20mA in 1 Relay contacts 24VAC...

Reviews: