IMPORTANT SAFETY INSTRUCTIONS 

 

When replacing the batteries, use the same number and the same type of batteries. 

 

Do not dispose of batteries in a fire; the battery may explode. 

 

Do not open or mutilate the battery or batteries, released electrolyte is harmful to the skin 

and eyes. 

 

A battery can present a risk of electric shock and high short circuit current. The following 

precaution should be observed when working on batteries. 
* Remove watches, rings or other metal objects. 
* Use tools with insulated handles. 

 

To prevent an overbalance of this unit, with the installation the additional stabilizer are to 

mount at the bottom side. 

 

This unit should be installed by service personnel. 

 

The equipment can be operated by any individuals with no previous experience. 

 

“The socket-outlet shall be installed near the equipment and easily accessible.” 

 

“With the installation of this equipment it should be prevented, that the sum of the leakage 

current of the UPS at the connected consumer does not exceed 3.5mA.” 

 

Attention:

 hazardous through electric shock. Also, with disconnection of this unit from the 

main, hazardous voltage still may be accessible through supply of battery. 

 

The battery supply should be therefore disconnected in the plus and minus pole through or 

from the outer enclosure accessible battery fuses when maintenance or service work 

inside the UPS is considered. 

 

The lead acid battery may cause chemical hazard. 

 

The battery presents a risk of electric shock and energy hazard. 

 

Batteries will be disposed by the manufacturer or importer.   Customers need to send 

them back with no charge for disposal. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

1

 

Summary of Contents for 5000VA

Page 1: ...PowerPrem Line interactive UPS User s Manual 5000VA 5K 02 0 ...

Page 2: ... operated by any individuals with no previous experience The socket outlet shall be installed near the equipment and easily accessible With the installation of this equipment it should be prevented that the sum of the leakage current of the UPS at the connected consumer does not exceed 3 5mA Attention hazardous through electric shock Also with disconnection of this unit from the main hazardous vol...

Page 3: ... in a dry place The admissible storage temperature range is 15 to 55 All handling operations will require at least two people unpacking installation in rack systems Once installed and connected to the AC power source for the first time the battery will start to charge Full charging to obtain the rated battery backup time requires at least 8 hours Before and after the installation if the UPS remain...

Page 4: ...erator s manual for additional information such as important operating and maintenance SAFETY EARTHING TERMINAL Indicates the primary safety ground RJ 45 RECEPTACLE For 230V units only this receptacle provides network interface connections Do not plug telephone or telecommunications equipment into this receptacle This symbol indicates that you should not discard the UPS or the UPS batteries in the...

Page 5: ...lation Page 9 4 Operation Page 12 5 Indication and Control Page 15 5 1 LCD Display Control 5 2 LCD Screen Description 5 3 Audible alarm Page 16 5 4 Auto self test Function Page 17 5 5 Remote Control 5 6 Reset the UPS 5 7 DIP Switch Settings 6 Communication interface Page 18 7 Trouble shooting Page 19 8 Specifications Page 20 5 ...

Page 6: ...iability the unique benefits of the UPS include the following Pure sine wave output Microprocessor based design with true Line Interactive structure Adjustable voltage sensitivity charging voltage voltage transfer points Remaining Estimated Backup Time indication EBT system on LCD version Smart battery management with intelligent double stages of charging control Real time auto detection for batte...

Page 7: ...2 PRESENTATION 2 1 Front Panel Tower Type Rack Mount Type LCD Display Main control button LCD screen Selection button for mode value 1 2 3 7 ...

Page 8: ...2 German type Schuko x 1 or B 2 IEC 5 sockets x 3 or B 3 Universal sockets 2 x 2 screw terminal x 1 C Re settable fuses for output D Re settable fuse for input E SNMP slot F Cooling fan G Communication port USB optional H RJ 11 port I DIP switch J Communication port RS 232 K Handles 8 ...

Page 9: ...first then put on the battery set one by one and finish the connection Ref 3 6 finally make connection for input and output of the UPS 3 4 The UPS can be used as a rack mount unit or a tower one Please follow the steps to make it as a rack mount unit or a tower one as below 3 4 1 Tower type To screw on the rubber pad 6pcs as enclosed at the bottom side of the unit or put on 4 wheels optional Botto...

Page 10: ...3 6 2 Inside view when front panel is removed 3 6 3 Please screw off the top cover of the battery set to be replaced change the batteries inside with the same spec number and make it in series connection DWG 3 6 3 Inside view of battery pack when top cover is removed 3 6 4 Put back the battery set in the main unit finish the connection with the UPS and proceed the same steps for replacing the othe...

Page 11: ...eantime if the overload is severe the UPS will shut down immediately for protecting UPS itself 3 9 If you are going to use the setting software i e UPS Wizard connect your computer to the communication port of UPS RS 232 with the supplied communication cable 3 10 After installation with normal city power the UPS will charge the battery automatically please keep the UPS in charging for 5 hours at l...

Page 12: ...batteries if the utility power is normal When utility power is normal please pull out the power cord if you want to turn off the UPS completely 4 5 To test the battery and inverter of UPS you can unplug the I P cord but it is more convenient to push the main control button for one second the UPS will simulate a 10 seconds blackout and transfer to battery mode for discharging test To cancel self te...

Page 13: ...he battery needs capacity balance discharge every 12 months which is to discharge the UPS batteries to low battery alarm by disconnecting the AC input with the UPS and use a table lamp as the load Do not use PC as the load when doing capacity balance discharge to prevent from data loss at low battery shut down The lower the load the better the balancing effect Note If an UPS is stored in stock ple...

Page 14: ...ty mode Sometimes when battery is empty after blackout the auto turn on function will have very short backup time if blackout happened again following with a short time recovery To select On S will provide Auto turn on only when the battery is charged for at least 30 of its capacity 4 11 5 To change the green mode level at battery mode When the Gn 0 is blinking it means the green mode level if off...

Page 15: ...r mode Test mode 3 The sine wave symbol will display steadily with blinking battery symbol when the UPS is in testing mode 5 Buck mode The AVR Auto Voltage Regulator is reducing the output voltage of the UPS when the input voltage is too high and the sine wave symbol as mentioned in item 4 will also display steadily to indicate that the output is in the normal mode 6 Boost mode The AVR is increasi...

Page 16: ... Function is executed 14 Battery voltage level 1 The higher the battery voltage the more bars will illuminate 2 When the UPS is charging the battery the battery symbol and the level indicator will blink together 15 Mode Value Description AC out V AC output voltage AC in V AC input voltage AC out Hz AC output frequency BATT V DC battery voltage TEMP UPS internal temperature TIMER Min to off The UPS...

Page 17: ...k and requires extended recharge 5 5 Remote Control The UPS can be set for daily shutdown wake up This command must be set through the RS 232 interface When this function is set the timer inside the UPS will begin to run and the load will be turned off by the shutdown wake up schedule During the period of turn off to the next turn on the time period to next turn on will be shown on LCD panel by ho...

Page 18: ... 2 1 9 8 7 6 Pin 6 RS 232 data Tx out Pin 7 Common of Pin 6 and Pin 9 Pin 9 RS 232 data Rx In 6 2 The definition and setup for DB9 optional is shown as follows Pin 2 AC Power Failure Pin 4 Common GND of Pin 2 Pin 5 Pin 5 UPS Battery Low Pin 6 Turn off UPS Pin 7 GND of Pin6 The interface with computer is diagramed as above for your reference Use Pin 4 as the common of Pin 2 and Pin 5 Pin 2 and Pin ...

Page 19: ...ected run time 1 Excessive loads connected at UPS s outlets 2 Battery is weak and cannot provide enough capacity Do not operate the UPS and leave the UPS plugged in for 10 hours Then test it again if UPS still cannot provide expected run time battery should be replaced Button on front panel doesn t work 1 The CPU inside UPS is not running correctly 2 Button damaged 1 Unplug the line cord push the ...

Page 20: ...le Voltage Waveform Sine wave Crest Factor 3 1 Output Frequency Synchronized to Mains Auto Select for 50 60Hz 47Hz 55Hz for 50Hz nominal 56Hz 65Hz for 60Hz nominal Regulation Nominal 5 typical of nominal voltage optional at 8 AVR for wide I P up to 35 Regulation Batt mode 3 of selected output voltage adjustable with the remote set up software Transfer time Blackout 3ms Brownout 1ms Battery mode to...

Page 21: ...t normal line and normal temperature Charging current 6A Max Average charging voltage for each battery Quick charging mode 14V maximum Trickle charging mode 13 2V 13 9V adjustable with the remote set up software Protection Over current protection Over charging voltage protection Thermal protection CPU control When temperature inside UPS is over 42 charger will stop charging for 2 minutes followed ...

Page 22: ...32 to 104 Transit storage Temp 15 to 55 5 to 131 Relative Humidity 5 95 non condensing Operating Altitude 0 3000 meters Audible noise 40 dBA at 1M from surface of unit Safety Markings CE BSMI EMC Class B EN50091 2 FCC part15 IEC1000 2 2 Quality control system ISO 9001 Physical Dimensions H W D Unit Shipping 4u x 52 cm Main unit 64 x 60 x 40cm battery packs 45 x 18 x 13cm 2sets Weight Net Gross kg ...