12
Submenu item
Function
SIMULATION:OFF
The purpose of this submenu to check dry contact connections. Normally to
check line failure contact you must turn off mains power. This is not necessary
with this utility. 3 options are available.
SIMULATION OFF simulation mode is off
SIM:LINE FAILURE if you press ENTER key for 3 seconds the line failure lamp
on interface board is turned on.
SIM:LIN.F+BT.LOW if you press enter key for 3 seconds the line failure and
battery low lamps on interface are turned on.
SIM:BYPASS if you press ENTER key for 3 seconds the bypass (aux) lamp on
interface board is turned on.
So you can check dry contact connections
ENTER>FAULT RST Faults reset selection.
<ENTER> EXIT
→
Enter
(
↵
↵↵
↵
) exit from submenu
5.3.2 MEASURES Menu items
All the measurements of the UPS can be monitored via this menu, navigation through the items is
performed using up and down buttons.
Submenu item
Function
LOAD ..: %
Output load percentage
OP.CURR: A
Output current
OUTPUT.:000 V
Output voltage
IPV:000 V
3 Phase input voltages
BATTERY: V
Battery voltage
BYPASS.: V
By-pass voltage
FR: HZ
Input frequency – Output frequency
TEMP.:000 C NORM
UPS Internal temperature
BAT.TIME:--- min
Battery time
<ENTER> EXIT
→
Enter
(
↵
↵↵
↵
) exit from submenu
5.3.3 ALARMS Menu items
The last 28 events can be monitored in this menu.
Submenu item
Function
UPS STATUS
Alarm status at that instant.
000> LOG EVENT
Monitoring past alarms:
First 3 digit number indicates the event number, 000 event is the last one.
Date is in ddmmyy and time is in hh:mm format.
On the second line, the alarm events on the first line are listed. Using
↔
button 128 events can be viewed.
PAR.ERR:
Parallel controller board error (If parallel hardware exists)
If this value is 0 then the parallel is OK
<ENTER> EXIT
→
Enter
(
↵
↵↵
↵
) exit from submenu