9
PowerPro HP300 Series User Manual
1.3 Technical Specifications
GENERAL SPECIFICATIONS
10
15
20
30
Output kVA
10
15
20
30
Output kW
8
12
16
24
Output Power factor
0,8
Parallel Operation
Up to 2 UPS (1 Redundant)
Hot Stand-by Operation
Up to 2 UPS (1 Redundant)
Battery charging temperature compensation
Optional
Emergency shutdown
available
INPUT
Number of phase
3 phase
Input voltage
220/380 Vac or 230/ 400 Vac 3 phase ,N
Voltage tolerance
+15% , -15%
By-pass voltage
220/380 Vac or 230/ 400 Vac 3 phase, N
Input frequency
50 Hz.
±
5%
RFI Level
EN 50091
Split bypass connection
available
OUTPUT
Number of phase
3 phase
Nominal Output voltage
220/380 Vac or 230/ 400 Vac 3 phase ,N
Voltage regulation tolerance
±
1%
Nominal Output frequency
50 Hz
Output frequency tolerance (line syncron)
±
2%
Output frequency tolerance (free running)
±
0,2%
Efficiency 100% Load
90%
Load Crest Factor
3:1
Total Harmonic Distortion (THD)
<3%
Overload
125% load 10 min.150% load 1 min.
BATTERY
Number of
30
Run time
Optional
Float charge voltage
405 Vdc
End of charge voltage
300 Vdc
Boost charge
available
Battery Test
1 time in 1 week (manuel test available)
Charge time
<5 hours at full load
Battery trip
available
INTERFACE
Communication
RS232(standart) RS485 (optional)
Up to 5 remote monitoring panel
Remote control
Dry contact Line failure,battery low,bypass,
EPO ,battery trip in/out
SNMP capability
Optional SNMP adapter
Modem connection
available
OTHER
Maximum temperature
0-40
°
C
Audible noise
<60 dBA
Humidity
%10-%90
Dimensions (HxWxD) (mm)
1145x485x675