6
PowerPro HP300 Series User Manual
NOTE:
The battery circuit breaker must be turn to “1” position when a voltage comes to the main.
If not in a second main failure the critical load will be without Voltage.
C. On maintenance by-pass:
UPS shutdown but the load connected to the unprotected
mains via
the maintenance by-pass supply line.
D. Parallel operation :
At least 2 UPS’s is installed to system for increasing security and redundancy
, they operates together and interactive.
1.2.2 The Power Configuration of UPS
The power switch location of the T-300P series UPS’s are shown in the figures 1.1-2-3-4 In the figure 1.2
external (split) by-pass block diagram is given. Optionally the static and mechanic by-pass line can be
connect to a different 3 phase AC source ( other UPS etc.),and the rectifier input is connected to generator or
mains voltage. If there is no other power supply static and mechanic by-pass line input (S2) and the rectifier
input connections will be connect to each other. (See figure 1.1)
During the normal operation except the maintenance by -pass switch, all the Switches will be at “1-On”
position (closed).
3 phase
load
output
Inverter
Rectifier
Static By-Pass
Static Transfer Switch
Maintenance Bypass
Mechanic transfer switch
3 Phase
Line
Input
Battery group
S3
S2
S1
S5
S4
3 Phase
By-Pass
Supply
Input
Figure 1.2
UPS Split (external) By-Pass Block Diagram