3. 

CAUTION : 

*

  The UPS is designed to power computer loads and the associated 

peripheral devices, such as monitors, modems, external H-Disk 
drivers, etc.  To ensure the performance of the UPS, Do Not load the 
UPS with laser printer, motor, or any type of inductive load. 

*

  Connecting the UPS to a two-pole, three-wire grounding mains 

receptacle.  Connection with any other type of receptacle may result 
in a shock hazard and may violate local electrical codes. 

*

  Do not allow water or any foreign object to get inside the UPS.  And 

do not put objects containing liquid on or near the unit. 

*

  Keep UPS away from fire or heating sources. 

*

  The UPS is shipped from the factory with fully charged internal 

batteries; however, the batteries may lose some energy during 
delivery and storage.  To ensure that the UPS will provide the 
expected run-time during a blackout, the UPS must be left in 
charging for at least 5 hours before your first use.  The batteries 
would be recharged automatically by the UPS when the UPS is 
connected with city power. 

 

 

 

4. 

INSTALLATION, OPERAT ION & AUDIBLE ALARM : 

4.1  Installation 

*

  Inspecting the packing carton for damage that may have occurred while 

in transit.  Immediately notify the carrier and place of purchase if any 
damage is found.  Retain the package for future use. 

*

  Plugging the power cord to a 3-wire grounding receptacle.  If an 

extension cord must be used between the UPS and the nearest wall 
outlet, use a 3-wire grounding type rated for at least 20 Amps. 

*

  Connecting your equipment to the UPS.  To ensure that your 

computer equipment will be protected during a utility failure, it is 
important to make sure that the maximum power need of the 
equipment is not over the rated capacity of the UPS.  When 
blackout happens, LED of operation status will become red and 
alarm will beep if the load is over the rated value.  Meantime, if the 
overload is severe, the UPS will shut down immediately for 
protecting UPS itself. 

 

 

 

 

 

 

7. TROUBLE SHOOTING 

Problem 

Possible Cause 

Action to Take 

UPS no reaction while 
AC is connected 
 
 

 

1.  Line cord plug is loose 
2.  Fuse on rear panel blown 

(Inside  the drawer of inlet) 

3.  Dead wall socket 

1. Check the line cord plug 
2. Replace fuse 
3. Check wall socket with a 

table lamp. 

Power output is normal, UPS 
emits continuous beep, and 
status LED shows RED. 

 

UPS is over loaded 

Turn off UPS and unplug 
excessive loads from UPS. 

UPS does not provide 
expected run time 

1. Excessive loads connected 

at UPS’s outlets. 

2. Battery is weak and 

cannot provide enough 
capacity. 

Do not operate the UPS, 
and leave the UPS plugged 
in for 10 hours.  Then, test it 
again, if UPS still cannot 
provide expected run time, 
battery should be replaced. 
 

Button on front panel 
doesn’t work  

1. The CPU inside UPS is 

not running correctly. 

2. Button damaged. 

1.

 

Push the button for 6 
seconds to reset the UPS. 

2.Unplug line cord and all 

loads from the UPS, and 
call for service. 

 

Under AC mode, UPS emits 
urgent beep (8 beeps per 
sec.) and replaces battery 
LED comes on. 

 

Battery is weak and should 
be replaced 

Replace batteries. 

No output when blackout 
happen. 
 
 

1.  Dead battery. 
2.  UPS NG. 

1. Replace battery. 
2. Call for service. 

 

 

 

5                                                                                     10 

Summary of Contents for PowerStar series 1200

Page 1: ...uptible Power System THE BRITISH POWER CONVE RSIONCOMPANY User s Manual PowerStar Series 1200 1700 2200 100 80 60 40 20 Replace Battery Alarm Off Charging B u c k Boost BATTERY LEVEL SPECIAL STATUS NORMAL BACK UP LOW BATT OVER LOAD ...

Page 2: ...ge 5 4 INSTALLATION AND OPERATION Page 5 6 4 1 Installation 4 2 Operation 4 3 Audible alarm 5 INDICATION AND CONTROL Page 7 8 5 1 Battery level LEDs 5 2 Special status LEDs 5 3 Auto self test function 5 4 Status LED and Alarm indication 5 5 Reset the UPS 6 COMMUNICATION INTERFACE Page 9 7 TROUBLE SHOOTING Page 10 8 SPECIFICATIONS Page 11 9 IMPORTANT SAFETY INSTRUCTIONS Page 12 MEMO 1 ...

Page 3: ...f battery voltage level LEDs of UPS special status LED of operation status Control button 2 1 3 4 2 1 4 NORMAL BACK UP LOW BATT OVER LOAD BATTERY LEVEL SPECIAL STATUS Replace Battery Alarm Off Charging B u c k Boost 100 80 60 40 20 3 13 2 ...

Page 4: ...ated by any individuals without any previous experience The socket outlet shall be installed near the equipment and easily accessible With the installation of this equipment it should be prevented that the sum of the leakage current of the UPS an the connected consumer does not exceed 3 5mA Attention hazardous through electric shock Also with disconnection of this unit from the main hazardous volt...

Page 5: ... cm 38 x 20 x 18 44 x 20 x 18 51 x 20 x 18 SHIPPING DIM L x H x W cm 48 x 33 x 30 54 x 33 x 30 61 x 33 x 30 WEIGHT N W G W kgs 15 16 21 50 22 50 25 26 1 INTRODUCTION 1 1 Overview The PowerStar series UPS is an advanced high performance stand by Uninterruptible Power System UPS designed to protect your computer from utility line failure In the event of utility failure blackout the UPS will rapidly ...

Page 6: ...rated for at least 20 Amps Connecting your equipment to the UPS To ensure that your computer equipment will be protected during a utility failure it is important to make sure that the maximum power need of the equipment is not over the rated capacity of the UPS When blackout happens LED of operation status will become red and alarm will beep if the load is over the rated value Meantime if the over...

Page 7: ...e of self test about 3 4 sec If test results are O K the green LED will be on 4 2 2 Pushing the button for 3 seconds the UPS will turn off the power But the red LED will remain blinking when the AC power cord is connected To turn off the power completely please pull out the power cord For turning on the UPS again please connect back power cord and push the button 4 2 3 During blackout push the but...

Page 8: ... connecting a low utility voltage The loads receive normal power The Buck LED would be on when the UPS is connecting a high utility voltage The loads receive normal power 5 3 Auto self test function In normal mode of UPS turn on your computer and push the button on the front panel for self test The UPS will simulate a power outage and transfer your load to the UPS s battery If low battery warning ...

Reviews: