SS-3N/BIR3/STD, SS-3N/BIR3/WH
Installation
6
9/7/2018
Bradley
• 215-1496 Rev. J; ECN 17-08-026
CODE
DESCRIPTION
QTY.
A
3/8" Wall Anchors with a minimum pull-out force of 1,000 lbs. for Bowl
2
B
3/8" Wall Anchors with a minimum pull-out force of 1,000 lbs. for Mainframe
6
C
3/8" Wall Anchors for Base Frame, Standard Frame option only, minimum pull-out force not
required
2
D1
1/2" nominal copper tubing for Cold Supply, stub-out 2" from wall
1
D2
1/2" nominal copper tubing for Hot or Tempered Supply, stub-out 2" from wall
1
E
1-1/2" NPT Drain, stub-out 2" from wall
2
F
On the bowl back, measure the distance between the ¾" bowl mounting holes. Divide this
measurement in half. Measure and mark this dimension on the wall to the left and the right
of the centerline. Install two 3/8" wall anchors with a minimum pull-out rating of 1,000 lbs
(supplied by installer) at locations marked.
2
RIM HEIGHT
VERTICAL HEIGHT ADJUSTMENTS FOR
CODES A–E, H, C and W
FIXTURE STYLE
34"
None
Standard Height
34"
None
Wall-Hung
32"
Subtract 2"
TAS, Grades 6 through 8 or 9
31"
Subtract 3"
Juvenile Height
30"
Subtract 4"
TAS, Pre-K through Grades 5 or 6
1
Rough-Ins
28-3/4"
(730)
32"
(813)
15"
(381)
4"
(102)
Floor
2-3/4"
(70)
24"
(610)
34"
(864)
Rim Height
See Chart
Below
38-1/2"
(978)
24-3/8"
(619)
B
B
B
B
C
C
E
F
B
D2
A
5-5/8"
(143)
B
38-1/2"
(978)
24-3/8"
(619)
8"
(203)
D1
F
A
3-1/2"
(89)