Terreon® Quadra-Fount® Washfountain with Touch Time® Control
Installation Instructions
MF2944/TT
9
Bradley Corporation • 215-1539 Rev. A; EN 03-063
12-18-2003
Installation Instructions continued . . .
Step 7: Electrical and supply connections
WARNING: The Touch Time control must be connected with a 24 VAC Class II
transformer. Connections to 110 VAC can cause personal injury and
will result in damage to the electronics.
CAUTION: Connection of leads other than shown may cause permanent damage
to the sensor.
IMPORTANT: Compliance and conformity to local codes and ordinance is the
responsibility of the installer.
1. Connect the wires per the wiring diagram shown below.
2. Insert four different colored sprayhead supply tubes into four solenoid tube connectors, as shown
in Figure 7, by loosening tube connector cap and firmly pushing tubing into tube connector until
the tubes are fully seated, then re-tighten connector cap.
Supply Inlet
Navigator® Mixing
Valve
Solenoid
Assembly
Transformer
S83-134
Green Supply Tube
(From Sprayhead)
Red Supply Tube
(From Sprayhead)
Black Supply Tube
(From Sprayhead)
Yellow Supply Tube
(From Sprayhead)
Left
Button
Compression
Nut
Compression
Nuts
Brown Wires
Black Wires
Green Wires
Gray Wires
Left
Center
Button
Right
Center
Button
Right
Button
Gray
Green
Black
Brown
Figure 7