background image

2

2.3

Setting the Heat Anticipator

NOTE:

 

 Some heating systems require a longer or shorter “ON/OFF” period to maintain comfort. 

Set the heat anticipator as specified in one of the following conditions:

•  For replacement installations match the anticipator setting with that of the thermostat being replaced.

•  For new installations match the current draw (amperage) of the heating control or relay. To do this check the rating 

  label on the control within the heating system. If the label cannot be found, determine circuit amperage by:

INSTALLATION

2

cont.

WARNING:

 Thermostat will not function if 

anticipator handle covers PC board cutout.

1.

  Place system lever in the 

HEAT

 position.

2.

  Adjust temperature lever until indicator is at least 3 degrees above the room temperature. The heating system should start  

  within several seconds. Fan may not turn on immediately due to the heating system built-in fan delay.

3.

  Place system lever in the 

OFF

 position. The heating system should stop within several seconds.

The adjustable heat anticipator will burn out if 25 Volts are applied directly to the thermostat by shorting out the gas valve 

or primary control during testing or by improper wiring.

WARNING!

TESTING YOUR NEW THERMOSTAT

3

WARNING!

Read BEFORE Testing

•   Do not short (or jumper) across terminals on the gas valve or at the heating or cooling system control board to test 

  the thermostat installation. This could damage the thermostat and void the warranty.

•   Do not select 

COOL

 mode of operation if the outside temperature is below 50° F (10° C). This could possibly 

     damage the controlled cooling system and may cause personal injury.

.2

.3

.4

.5

.6

.8

1.0

LO

N

G

ER

 CY

CLE

S

1.

  Slide the system lever to 

OFF

, or set temperature to lowest setting  

  so that the contacts are open. Make sure system power is  

  turned back on.

2.

  Set an AC ammeter to the 0 to 1 amp. range. Place the meter  

  probes on W and Rh terminals. The heating valve or relay will turn  

  “ON” and a reading will appear on the meter. Note this reading. 

  Remove the probes from the terminals.

3.

  Set the heat anticipator arrow to this meter reading. This is the  

  normal setting.

4.

  The anticipator adjustment must be made so that the thermostat  

  is in “balance” with the rest of the system. It will determine how  

  often the heating system turns on and off.

NOTE:

 

 If installing on a millivolt heat only system, set the 

anticipator to the maximum setting of 1.2.

NOTE:

 

 Allow the heating system to operate for a full day or more. 

Too frequent cycling of the heating system can result in lower life 

expectancy for the heating system.  If adjustments are necessary, 

make them in 0.1 amp increments at a time. Move the anticipator 

lever in direction of arrow to cycle less often.

3

5

SYMPTOM

POTENTIAL SOLUTION

Thermostat does not turn 

on heating or cooling 

system.

Thermostat turns on 

heating instead of cooling, 

or cooling instead of 

heating.

Check thermostat wiring to be sure that the heating and cooling stages are connected to the 

correct terminals. See 

Installation 

and

 Wiring Diagrams

 sections of this manual.

Thermostat turns heating 

system on too often or not 

often enough.

Increase or decrease anticipator setting as appropriate to provide the desired performance 

level. See 

Setting Heat Anticipator

 section of this manual.

Fan continues to run all 

the time whether the 

system is on or off.

Check that the fan control lever is in the 

AUTO

 position. This will allow the fan to run only 

when the heating or cooling system is turned on and running.

Check thermostat wiring to make sure that the fan control wiring is connected to the correct 

terminal. See 

Installation 

and

 Wiring Diagrams 

 sections of this manual.

Check to see if system lever is in the 

OFF

 position. This indicates that the system is turned 

OFF

 at the thermostat. Move the system lever to either the 

HEAT

 or 

COOL

 position.

Heating or cooling system may be malfunctioning. Call a professional service technician 

immediately to verify system operation.

TESTING YOUR NEW THERMOSTAT

3

cont.

4.

  Place system lever in the 

COOL

 position. 

5.

  Adjust temperature lever until indicator is at least 3 degrees lower than room temperature. The cooling system should  

  start within several seconds.

6.

  Place system lever in the 

OFF

 position. The cooling system should stop within several seconds.

7.

  Place fan lever in the 

ON

 position. The system blower should start.

8.

  Place fan lever in the 

AUTO

 position. The system blower should stop.

For heat pumps, 

DO NOT

 place system lever back in the 

HEAT

 position. Quick repetitive cycles of the system compressor can 

lead to damage and shorten its life expectancy. 

DO NOT

 place the system lever back in the 

COOL

 position. Quick repetitive cycles of the cooling system compressor can lead 

to damage and shorten its life expectancy. 

WARNING!

WARNING!

1.

  Set the system lever to either 

HEAT

 or 

COOL

.

2.

  Adjust the temperature lever to the desired setpoint temperature.

4

USING YOUR NEW THERMOSTAT

TROUBLESHOOTING

Reviews: