background image

 

 UNI EN ISO  9001-2015 n°  9115.BRMO

 

UPS OCTANS 10/20kVA 3:1 

USER MANUAL 

 

File name 

Date 

Page 

 
Code 
 
 

PUV9E010/15/20-AK 

DF19010A 

10/04/2019 

1 di 28 

MD03006C

 

All rights are reserved according to the law. Reproducing or distributing this document to third parties without permission is prohibited.

 

 

 

 

VIA LUDWING VAN BEETHOVEN N.24 

 

20090 CINISELLO BALSAMO (MI) 

 

Tel.: +39 0251672201 
Fax: +39 0251672213 

 

Mail: 

sales@bragamoro.com

 

www.bragamoro.com

 

 

 

USER MANUAL 

 

 

 OCTANS PLUS 15/20kVA 3:1 

 

 

 

 

Summary of Contents for OCTANS PLUS 10k

Page 1: ...19 1 di 28 MD03006C All rights are reserved according to the law Reproducing or distributing this document to third parties without permission is prohibited VIA LUDWING VAN BEETHOVEN N 24 20090 CINISELLO BALSAMO MI Tel 39 0251672201 Fax 39 0251672213 Mail sales bragamoro com www bragamoro com USER MANUAL OCTANS PLUS 15 20kVA 3 1 ...

Page 2: ... 5 3 Connection of parallel system 12 6 Operation 13 6 1 Working modes 13 6 1 1 AC mode 13 6 1 2 Bypass mode 13 6 1 3 Battery mode 13 6 1 4 ECO mode 13 6 2 Panel display operation and running 14 6 2 1 Start up and turn off the UPS 14 6 2 2 Faceplate display 15 3 Display instruction 17 6 3 Working Mode and transferring 20 6 3 1 Transfer to bypass if overload 20 6 3 2 Normal mode to battery mode 20 ...

Page 3: ...tributing this document to third parties without permission is prohibited 1 DOCUMENT CHECK SECTION Drawing Written by Role Date David Alessandri Technical Staff 10 04 2019 Control Controlled by Role Date David Alessandri Technical Staff 10 04 2019 Approved Approved by Role Date Adelio Abbondio Technical Staff 10 04 2019 Revision Rev Author Description Date B C D E F G H I L References Ref Author T...

Page 4: ...F THE TECHNICAL DESCRIPTION OR THE DATA SHOWN BECAUSE THERE IS NO OBLIGATION FOR THE PERMANENT UPDATE OF THIS DOCUMENTATION BEFORE INSTALLING OR OPERATING THIS EQUIPMENT READ THE INSTRUCTIONS CONTAINED IN THIS MANUAL CAREFULLY AND MAKE SURE THEY ARE RESPECTED BY TECHNICAL PERSONNEL KEEP THIS MANUAL CLOSE TO THE EQUIPMENT FOR EVERY FUTURE REFERENCE ALL MAINTENANCE WORKS MUST BE CARRIED OUT BY QUALI...

Page 5: ...guration of the connections 3 MAKE SURE THE EARTH CONNECTIONS ARE WELL DONE BEFORE TURNING THE UPS ON 4 The operating and storage environment may affect the reliability of the UPS 5 Avoid placing the UPS and operating it in the following environments Areas with temperatures and humidity outside the range stated in the specifications on page 29 Areas where the UPS is exposed to direct sunlight or n...

Page 6: ...ed for computer center network management center auto control system telecom systems etc 4 2 Product range This series contains many capacities of UPS products The UPS models and configuration of 10 k 15 k 20 k are as follows Capacity 10kVA 15kVA 20kVA Model 10k 15k 20k Remarks Standard model External battery Standard model External battery Standard model External battery 4 3 System principle diag...

Page 7: ...output will not be disturbed by power network suitable for area with poor power supply condition DSP technology for all digital control high reliability self diagnostics and protections are featured Intelligent battery management which extends battery life LCD panel and LED indicators clearly indicate the system status and parameters such as input output voltage frequency load temperature inside U...

Page 8: ...he law Reproducing or distributing this document to third parties without permission is prohibited 4 5 2 Rear panel instruction 4 5 2 1 10 15 20k H Rear panel 1 2 3 4 5 7 8 9 6 Fig 4 5 2a 10 15 20 k H Rear Instruction 1 Intelligent slot 2 EPO External Power Off 3 Parallel port 1 4 Parallel port 2 5 Input output breaker 6 COM 7 USB 8 Maintenance bypass switch covered 9 Terminals covered ...

Page 9: ...or equipment or other object Don t block the ventilation holes of the UPS located in the front panel and the bottom part so as to keep the ventilation in good condition avoid temperature of components inside getting high Keep the UPS away from high temperature water flammable gas corrosive gas dust direct sunlight and explosive things Don t lay the UPS outdoor 3P 125A 400V circuit breaker is requi...

Page 10: ...ttery bank after finishing connection CAUTION Don t mix batteries with different capacity brands and don t mix brand new and old batteries either 2 The breaker on battery cabinet should be off 3 Take out the connection box and remove the cover of terminals use multi meter to make sure there is no DC voltage at the battery terminals of UPS 4 Connect battery pole with positive pole common pole and n...

Page 11: ...k H External battery connection 5 2 2 2 UPS input and output connection Minimum 8AWG or 10 mm2 copper wires for input output battery cables are required for the ups Switch off all breakers before connecting cables Remove the cover of the terminals see Fig 2 4 and connect the cables correspondingly A B C Ni Lo No BAT BATN BAT INPUT A INPUT B INPUT C INPUT N OUTPUT L BATTERY BATTERY N BATTERY OUPUT ...

Page 12: ...tput L N E to L N E of load via a PDU Tighten the screws and shelter the terminals CAUTION Please connect the output Earth well before go for other operation 5 2 2 3 Connection of the UPS communication cables 1 USB cable provided in accessories can be used to connect the UPS with PC 2 Follow steps below to install SNMP if purchased a Remove the cover of SNMP slot at UPS rear panel and keep it for ...

Page 13: ... of the generator 2 It is suggested that the rating of generator should be 1 5 2 times of the capacity of the UPS 6 1 2 Bypass mode When the AC power is connected and the UPS has not been switched on or the UPS is overloaded after switching on the UPS it will go to bypass mode The Loads will be powered by AC battery will be charged and the bypass indicator on the LCD control panel will be on yello...

Page 14: ...he UPS 2 Turn on the UPS in Battery Mode Press On on the front panel to start the UPS and in the meantime the LCD display will light up You may view the data and set parameters on the LCD display and the LED display of the UPS will show the latest status of the UPS Turn off operation 1 Turn off the UPS in line mode without batteries Press and hold the OFF key for 2 seconds to turn off the inverter...

Page 15: ...AC Indicator 12 Bypass Indicator 13 Fault Indicator LCD display 1 LED indicator definition 1 Fault Indicator red On indicates when a fault occurred Off means no fault occurred 2 Indicator Green On means AC is normal Off means AC is not present and blinking means voltage is beyond normal range 3 Inverter Indicator Green On means when load is powered by inverter Off means when it is not working and ...

Page 16: ...35V per cell floating charging voltage 2 20 to 2 29V per cell 2 Battery capacity setting includes the Ah of each battery unit battery quantity 8 to 10 2 parallel group number low battery voltage alarm value EOD 3 Parallel setting 4 UPS ID setting 4 Button Definition Button Definition ON Switch on the inverter by pressing and holding it for 1s when the UPS is off OFF Switch off the inverter output ...

Page 17: ... interface 3 Press the ENT button it will change to main menu see Fig3 Fig 3 Main menu 4 An arrow icon will come out on the LCD when pressing the ENT then the data info status info setting info can be selected by pressing the right or left arrow button and checking the details by pressing 5 Select and confirm the data info to be viewed in detail It contains the details of the AC input output inver...

Page 18: ...rmation alarm information code power rating and version See Fig 14 to 15 Fig 14 main menu Fig 15 main menu 7 Select and confirm setting menu setting information will be displayed on the screen which includes user set system set parallel set battery sett revise set See Fig 16 to 24 Fig 16 setting menu Fig 17 setting menu FIGURE Invert 220 0V 50 0Hz FIGURE P Battery 0V 0 0A 0min 0 FIGURE N Battery 0...

Page 19: ...distributing this document to third parties without permission is prohibited Fig 18 setting menu Fig 19 setting menu Fig 20 Parallel setting Fig 21 Batter self Test Off Fig 22 Batter self Test ON to 10 seconds Fig 23 Batter self Test ON to 10 minutes Fig 24 Batter self Test ON to EOD SETTING Parallel set ID 1 P amount 2 P Redund 0 SETTING BatTest Off SETTING BatTest 10s SETTING BatTest 10m SETTING...

Page 20: ...de fault indicator will be on red the LCD will display that the inner temperature is high long beeps will come If so please cut off the input power of the UPS move objects that affecting the ventilation far from the UPS if any or increase the distance between the UPS and the wall Wait until the UPS temperature becomes normal then restart it 6 3 4 Output short circuit When the UPS output is in shor...

Page 21: ...uously Fault LED lit 6 Bypass Thyristor broken Beep continuously Fault LED lit 7 Fuse broken Reserved Beep continuously Fault LED lit 8 Parallel relay fault Beep continuously Fault LED lit 9 Fan fault Beep continuously Fault LED lit 10 Reserved Beep continuously Fault LED lit 11 Auxiliary power fault Beep continuously Fault LED lit 12 Initialization fault Beep continuously Fault LED lit 13 P Batte...

Page 22: ... LED blinking 28 Bypass reverse Reserved Once per second Fault LED blinking 29 Output Short circuit Once per second Fault LED blinking 30 Rectifier over current Once per second Fault LED blinking 31 Bypass over current Once per second BPS LED blinking 32 Overload Once per second INV or BPS blinking 33 No battery Once per second BATTERY blinking 34 Battery under voltage Once per second BATTERY blin...

Page 23: ... 20 optional 230V 20 10 15 optional 240V 15 10 optional Min 45 20 30 optional Bypass frequency range 1 2 4 5 10 DC INPUT Battery number 16 18 20 pieces Battery type VRLA Charge model Boost charge or float charge auto switch Charge time Boost charge up to 20 hour Max Charge current MAX 1A S 10A H AC OUTPUT Output type 1 phase 3 wires Voltage regulation 1 0 Voltage distortion THD less than 2 at 100 ...

Page 24: ... 5 0 Dynamic respond 40ms output voltage DC component 100mV Transfer time Between Normal and battery mode 0ms Between inverter and bypass 0ms synchronous 15ms 50Hz 13 33ms 60Hz asynchronous Noise 55dB 1m Display LCD LED Safety Meet up with STANDARD IEC62040 1 Max input voltage 320Vac 1 hour static EMI Conduction IEC 62040 2 Radiation IEC 62040 2 Harmonics IEC 62040 2 EMS IEC 62040 2 MTBF 250 000 h...

Page 25: ...tion If the environment temperature is high charge it once every 2 months 4 For extended backup models check and clean the battery connectors periodically If backup time has become much less than before or there is battery fault displayed on the LCD please contact distributors to confirm whether the batteries are needed to be replaced or not CAUTION Before replacing batteries first please turn off...

Page 26: ... normal but AC indicator off the UPS is in battery mode A Input circuit breaker off B Input power connection problem A Switch on the input breaker B Check the connection and re do 3 No alarm but no output Output connection problem Check the connection and re do 4 The UPS doesn t start after pressing On button A pressing ON button time is insufficient B Overload A Press and hold On button for 1s B ...

Page 27: ...w Reproducing or distributing this document to third parties without permission is prohibited 10 Appendix I USB communication port definition Definition of Male port Pin 1 VCC Pin 2 D pin 3 D Pin 4 GND Application use UPSilon2000 Power Management software Available functions of the USB Monitor UPS power status Monitor UPS alarm info Monitor UPS running parameters Timing off on setting 1 2 3 4 ...

Page 28: ...prohibited 11 Appendix II RS232 communication port definition Definition of Male port Connection between PC RS232 port and UPS RS232 port PC RS232 port UPS RS232 port Pin 2 Pin 2 UPS send PC receive Pin 3 Pin 3 PC send UPS receive Pin 5 Pin 5 ground Available function of RS232 Monitor UPS power status Monitor UPS alarm info Monitor UPS running parameters Timing off on setting RS 232 communication ...

Reviews: