Mounting:

Mount the valve in a location with sufficient clearance 

to remove the weather shield cover and actuator. 

Before installing the electric actuator, use an adjustable 

wrench to manually rotate the valve stem several 

times. Rotating the valve stem breaks the torque that 

may have built up during long-term storage.
To mount the Small Weather Shield Kits: 
1. Position the valve ball and stem to the preferred 

spring return position. To mount the actuator to 

Spring Return Port A (Coil) Open, turn the valve 

stem to the position in Figure 4. To mount the 

actuator to Spring Return Port A (Coil) Closed, turn 

the valve stem to the position in Figure 5.   

Note:

Position the valve ball stem to the position in 

Figure 4.
2. Place the Teflon® thermal barrier on the ball valve 

actuator mounting flange by inserting the alignment 

rib on the bottom of the thermal barrier into the 

recess on mounting flange (Figure 6).

3. Install the valve adapter bracket over the thermal 

barrier and attach the valve adapter bracket to the 

valve using the four M6 screws and flanged nuts 

(Figure 7). Tighten screws to a recommended 

torque of 35 to 44 lb·in. (4.0 to 5.0 N·m).

Note:

Before you fully tighten the screws, temporarily 

install the valve shaft through the adapter bracket and 

engage the valve stem. This action ensures proper 

alignment with the valve stem and adapter bracket.

Figure 4:  Positioning the Valve Stem - 

Spring Return Port A (Coil) Open

3 Way

2 Way

2 Way

3 Way

Figure 5:  Positioning the Valve Stem - 

Spring Return Port A (Coil) Closed

Figure 6:  Mount the 

Thermal Barrier

Figure 7:  Install Valve Bracket

Reviews: