INSTALLATION
INSTALLATION
9
E. INSTALLATION THROUGH SIDE OF MASONRY CHIMNEY
NOTE:
Follow L-Vent chimney manufacturer’s instructions.
1. Position the stove, adhering to the clearances in Figure 1. Mark the
center of the hole where the pipe is to pierce the masonry chimney.
2. It will be necessary to break out the masonry around the location of the
pipe center mark. Use a 4-inch diameter hole for 3-inch pipe and 5-inch
diameter hole for 4-inch pipe.
3. Measure and build chimney top plate. Cut out holes for chimney pipe,
and if used, the outside air pipe.
4. Install the tee on the bottom of the vertical pipe system and lower it
down the chimney until the center branch of the tee is level with the
center of the hole in the masonry, as shown in Figure 10.
5. Install and seal the top plate from Step 3 with non-hardening mastic.
Slip the storm collar over the pipe, and while holding the pipe at the
proper elevation, af
fi
x the collar with a minimum of 3 1/4” stainless steel
sheet metal screws. Seal all joints and seams around the collar.
6. Connect the horizontal pipe by pushing it through the hole in the ma-
sonry and lining it up with the branch in the tee. Push the pipe into the
tee while twisting it to lock it into the tee.
7. If desired, once the horizontal pipe is in place, the space between the
pipe and masonry may be
fi
lled with high-temperature grout.
8. Install the trim collar. An adjustable pipe length and adapter may be
needed to
fi
nish the connection to the stove.
ELECTRICAL INSTALLATION
This stove is provided with a 6-foot grounded electrical cord
extending from the rear of the stove.
We recommend connecting to a good quality surge protector
that is plugged into a standard three-prong, 120V, 60Hz elec-
trical outlet.
DO NOT connect the unit to a GFCI socket.
Voltage variations can lead to serious performance problems. The
Breckwell electrical system is designed for 120V AC with no more
than 5% variation. Breckwell cannot accept responsibility for poor
performance or damage due to inadequate voltage. If connected
to an older, two-prong outlet, a separate ground wire should be
run to a proper ground (refer this to a quali
fi
ed technician). Always
route the electrical cord so that it will not come in contact with any
hot part of the stove.
FIGURE 9
FIGURE 10
6”
3”
TOP PLATE
(SEAL TO CHIMNEY TOP
WITH NON-HARDENING
MASTIC)
NOTE:
FOLLOW METAL
CHIMNEY INSTALLATION
INSTRUCTIONS
EXTENSION TO CHIMNEY TOP
REQUIRED.
3 OR 4 INCH STAINLESS STEEL
SINGLE WALL PIPE OR FLEX PIPE.
6”
BLANKING PLATE (SEAL WITH
NON-HARDENING MASTIC).
3 OR 4 INCH STAINLESS STEEL
FLEX PIPE.
OPTIONAL OUTSIDE AIR
CLEAN-OUT-TEE (TYPE L)
OR 90 DEGREE ELBOW
HEARTH
TOP PLATE
(SEAL TO CHIMNEY TOP
WITH NON-HARDENING
MASTIC)
6”
3”
NOTE:
FOLLOW METAL
CHIMNEY INSTALLATION
INSTRUCTIONS
EXTENSION TO CHIMNEY TOP
REQUIRED.
L-VENT OR OPTIONAL
3 OR 4 INCH STAINLESS STEEL
SINGLE WALL PIPE OR FLEX PIPE.
OPTIONAL OUTSIDE AIR
TRIM COLLAR
PIPE ADAPTER
CLEAN-OUT TEE (TYPE L)