DEFINING VOLTAGE DIPS, SURGES AND CUT-OFFS
Voltage dips and overvoltage (voltage surges) are stored as per IEC161000-4-30 and EN50160 with a Class B
measurement method
>
Voltage dips
The voltage dips threshold can be set to between 5% and 95 % of the reference voltage value.
Likewise, the dip is considered as terminated when it passes over the dip threshold, plus the voltage hysteresis.
>
Overvoltage
The overvoltage is threshold can be set to 105%-150% of the reference voltage value.
The overvoltage is terminated when it is under the dip threshold, less the voltage hysteresis
>
Voltage cut-offs
It is considered that there is a voltage cut-off if one of the phases is lower than minimum of measurement of
Dpa96
(see
Dpa96
technical characteristics).
PROGRAMMING
SYNCHRONISATION SIGNAL -
Example : MEMO TIME = 10’
x 1
x 1 (20 min)
x 2 (30 min)
x 3 (5 min)
x 4 (8 min)
x 5 (10 min)
x 6 (15 min)
x 1
confirm
RUDOLF - Ref. : 876 588 A
R-DPA96 A/AN - R-Module 7 (M
emory)
160
Summary of Contents for Rudolf R-DPA96 A
Page 25: ...25 R DPA96 A AN RUDOLF Ref 876 583 A DPA96A DPA96A DPA96A DPA96A x 1 x 2 x 3 x 4 OPERATION...
Page 27: ...27 R DPA96 A AN RUDOLF Ref 876 583 A DPA96A DPA96A DPA96A x 9 x 10 x 11 DPA96A x 12 OPERATION...
Page 28: ...28 RUDOLF Ref 876 583 A R DPA96 A AN DPA96A DPA96A DPA96A x 3 x 1 x 2 OPERATION...
Page 43: ...43 RUDOLF Ref 876 584 A...
Page 44: ...44 RUDOLF Ref 876 584 A...
Page 53: ...53 SOCOMEC R f 876 585 A...
Page 54: ...54 SOCOMEC R f 876 585 A...
Page 129: ...129 RUDOLF Ref 876 341 A...
Page 130: ...130 RUDOLF Ref 876 341 A...
Page 139: ...139 RUDOLF Ref 876 586 A...
Page 140: ...140 RUDOLF Ref 876 586 A...
Page 152: ...152 RUDOLF Ref 876 587 A...
Page 168: ...OPERATION DPA96A DPA96A RUDOLF Ref 876 588 A R DPA96 A AN R Module 7 Memory 168...