CONNECTION TEST FUNCTION
x 1
3 sec.
DPA96A
During the test, the R-DPA96 A/AN must have cur-
rent and voltage for each of the phases.
In addition to this, the function recognises the PF of
the installation as being between 0.6 > PF < 1. If the
PF of the installation is not within this range, this
function cannot be used.
In 4 BL/3 BL/2BL/1 BL, the connection of the CTs is
controlled only.
In 4NBL and 3NBL the connection as a whole is
controlled.
Do check that these are the right conditions:
Err 0
= no error
Err 1
= CT phase 1 inverted
Err 2
= CT phase 2 inverted
Err 3
= CT phase 3 inverted
Err 4
= V1 and V2 voltages inverted
Err 5
= V2 and V3 voltages inverted
Err 6
= V3 and V1 voltages inverted
For the Err 1, Err 2 and Err 3, the modification can
be performed automatically by the R-DPA96 A/AN or
manually by correcting the current connections.
For the Err 4, Err 5 and Err 6 the modification must
be performed manually by correcting the voltage
connections.
Example : tEsT Err 0
x 1
3 sec.
x 1
3 sec.
R-DPA96 A/AN
Summary of Contents for Rudolf R-DPA96 A
Page 25: ...25 R DPA96 A AN RUDOLF Ref 876 583 A DPA96A DPA96A DPA96A DPA96A x 1 x 2 x 3 x 4 OPERATION...
Page 27: ...27 R DPA96 A AN RUDOLF Ref 876 583 A DPA96A DPA96A DPA96A x 9 x 10 x 11 DPA96A x 12 OPERATION...
Page 28: ...28 RUDOLF Ref 876 583 A R DPA96 A AN DPA96A DPA96A DPA96A x 3 x 1 x 2 OPERATION...
Page 43: ...43 RUDOLF Ref 876 584 A...
Page 44: ...44 RUDOLF Ref 876 584 A...
Page 53: ...53 SOCOMEC R f 876 585 A...
Page 54: ...54 SOCOMEC R f 876 585 A...
Page 129: ...129 RUDOLF Ref 876 341 A...
Page 130: ...130 RUDOLF Ref 876 341 A...
Page 139: ...139 RUDOLF Ref 876 586 A...
Page 140: ...140 RUDOLF Ref 876 586 A...
Page 152: ...152 RUDOLF Ref 876 587 A...
Page 168: ...OPERATION DPA96A DPA96A RUDOLF Ref 876 588 A R DPA96 A AN R Module 7 Memory 168...