33
RUDOLF - Ref. : 876 583 A
TECHNICAL CHARACTERISTICS
CASE
Dimensions:
96 x 96 x 60 mm
or 96 x 96 x 80 mm with all optional modules (DIN 43700)
Connection:
via 2.5 mm
2
disconnectable terminals
(voltage and others) and 6 mm
2
fixed terminals (current)
IP index:
IP52 (front panel) and IP30 (case)
Weight:
400 gr.
DISPLAY
Type :
Backlit LCD display
MEASUREMENTS
Three-phase (3 or 4 wires), two-phase (2 wire) and single-phase networks
VOLTAGE (TRMS)
Direct measurement:
from 18 to 700 V AC (phase/phase)
from 10 to 404 V AC (phase/neutral)
Measurement via PT:
• Primary:
up to 500 kV
• Secondary:
60, 100, 110, 115, 120, 173 and 190 V AC
Display and resolution
from 0 to 500.0 kV
Permanent overload:
760 V AC
Update period:
1 second
CURRENT (TRMS)
Via CT with:
• Primary:
up to 10000 A
• Secondary:
1 or 5 A
Minimum measuring current
10 mA
Input consumption:
< 0.3 VA
Display:
from 0 to 11 kA (1.1 times the primary value)
permanent overload:
10 A
intermittent overload:
10 In / 1 second
Update period:
1 second
Maximum ratio KI x KU:
10 000 000
POWER
Total:
0 to 8000 MW/Mvar/MVA
Update period:
1 second
FREQUENCY
from 45,0 to 65,0 Hz
Update period:
1 second
ENERGY / MEASUREMENT ACCURACY
Current:
0.2 % from 10 to 110 % / In
Voltage:
0.2 % from 140 to 700 V AC
Power:
0.5 % of full scale (-90° à + 90°)
Power factor:
0.5 % for 0.5 < FP < 1
Frequency:
0.1 % from 45 to 65 Hz
Active energy metering:
± 0.5 % from 0.02 to 1,2 In with PF = 0.5 L or 0.8 C
(class 0.5S IEC 62053-22)
Reactive energy metering:
± 2% from 0.1 to 1,2 In with sin
ϕ
= 0.5 L or C
(class 2 IEC 62053-23)
AUXILIARY SUPPLY
110 to 440 V AC 50/60 Hz
± 10 %
120 to 350 V DC
± 20 %
12 to 48 V DC
-6 % / + 20 %
Consumption:
< 10 VA
R-DPA96 A/AN
Summary of Contents for Rudolf R-DPA96 A
Page 25: ...25 R DPA96 A AN RUDOLF Ref 876 583 A DPA96A DPA96A DPA96A DPA96A x 1 x 2 x 3 x 4 OPERATION...
Page 27: ...27 R DPA96 A AN RUDOLF Ref 876 583 A DPA96A DPA96A DPA96A x 9 x 10 x 11 DPA96A x 12 OPERATION...
Page 28: ...28 RUDOLF Ref 876 583 A R DPA96 A AN DPA96A DPA96A DPA96A x 3 x 1 x 2 OPERATION...
Page 43: ...43 RUDOLF Ref 876 584 A...
Page 44: ...44 RUDOLF Ref 876 584 A...
Page 53: ...53 SOCOMEC R f 876 585 A...
Page 54: ...54 SOCOMEC R f 876 585 A...
Page 129: ...129 RUDOLF Ref 876 341 A...
Page 130: ...130 RUDOLF Ref 876 341 A...
Page 139: ...139 RUDOLF Ref 876 586 A...
Page 140: ...140 RUDOLF Ref 876 586 A...
Page 152: ...152 RUDOLF Ref 876 587 A...
Page 168: ...OPERATION DPA96A DPA96A RUDOLF Ref 876 588 A R DPA96 A AN R Module 7 Memory 168...