63
RUDOLF - Ref. : CDR 27 028_gb
R-DPA96 A/AN - R-MODULE 3 (RS485 - JBUS/MODBUS
®)
COMMUNICATION
LIST OF PARAMETERS TO BE DISPLAYED (FUNCTION 3)
Address available with the Monitoring or Control/Command option
Decimal
Hexa.
Number
Text
Unit
address
address
of words
866
362
2
Input pulse meter 1
–
868
364
2
Input pulse meter 2
–
870
366
2
Number of impulse meters
–
872
368
2
Current alarm :
–
0 : no alarm
1 : I
2 : U
3:
Σ
P+
4:
Σ
Q+
5:
Σ
S
6: F
7 :
Σ
PFL
8 : thd I
9 : thd U
10 : In
11 : HOUr
12 : V
13 : thd In
14 : thd V
15 :
Σ
P-
16 :
Σ
Q-
17 :
Σ
PFC
874
36A
2
Current overrun :
–
0 : no alarm
1 : I
2 : U
3:
Σ
P+
4:
Σ
Q+
5:
Σ
S
6: F
7 :
Σ
PFL
8 : thd I
9 : thd U
10 : In
11 : HOUr
12 : V
13 : thd In
14 : thd V
15 :
Σ
P-
16 :
Σ
Q-
17 :
Σ
PFC
876
36C
2
Number of inputs-outputs
-
Low-order: number of inputs
High-order: number of outputs
878
36E
2
Status of inputs-outputs
–
0 : status input 1 (0 = open, 1 = closed)
bit 1 : status input 2 (0 = open, 1 = closed)
bit 2 : status input 3 (0 = open, 1 = closed)
bit 3 : status input 4 (0 = open, 1 = closed)
bit 4 : status input 5 (0 = open, 1 = closed)
bit 5 : status input 6 (0 = open, 1 = closed)
bit 16 : status output 1 (0 = open, 1 = closed)
bit 17 : status output 2 (0 = open, 1 = closed)
bit 18 : status output 3 (0 = open, 1 = closed)
bit 19 : status output 4 (0 = open, 1 = closed)
bit 20 : status output 5 (0 = open, 1 = closed)
bit 21 : status output 6 (0 = open, 1 = closed)
Summary of Contents for Rudolf R-DPA96 A
Page 25: ...25 R DPA96 A AN RUDOLF Ref 876 583 A DPA96A DPA96A DPA96A DPA96A x 1 x 2 x 3 x 4 OPERATION...
Page 27: ...27 R DPA96 A AN RUDOLF Ref 876 583 A DPA96A DPA96A DPA96A x 9 x 10 x 11 DPA96A x 12 OPERATION...
Page 28: ...28 RUDOLF Ref 876 583 A R DPA96 A AN DPA96A DPA96A DPA96A x 3 x 1 x 2 OPERATION...
Page 43: ...43 RUDOLF Ref 876 584 A...
Page 44: ...44 RUDOLF Ref 876 584 A...
Page 53: ...53 SOCOMEC R f 876 585 A...
Page 54: ...54 SOCOMEC R f 876 585 A...
Page 129: ...129 RUDOLF Ref 876 341 A...
Page 130: ...130 RUDOLF Ref 876 341 A...
Page 139: ...139 RUDOLF Ref 876 586 A...
Page 140: ...140 RUDOLF Ref 876 586 A...
Page 152: ...152 RUDOLF Ref 876 587 A...
Page 168: ...OPERATION DPA96A DPA96A RUDOLF Ref 876 588 A R DPA96 A AN R Module 7 Memory 168...