96
RUDOLF - Ref. : CDR 27 028_gb
R-DPA96 A/AN - R-Module 3 (
RS485 - JBUS/MODBUS
®
)
COMMUNICATION
PULSE METERS VALUES
Input meters
R-DPA96 A/AN
reply: identical to the message sent.
Size of this zone: 12 words (decimals) or C (hexadecimals)
RESET TO ZERO: ENERGY METERS AND MAX. VALUES (FUNCTION 6)
SAVED COMMAND (RESET)
The following command should be done to save
programming parameters changes for
R-DPA96
num-
ber 5.
NB :
R-DPA96 A/AN
will not reply to this command.
NB:
To reset several parameters to zero, add the corre-
sponding figure indicated in the “text” column.
Example: reset Max P+ and kvarh + to zero:
2 + 100 = 102 (Hex)
Example:
To reset all values for
R-DPA96
number 5 to zero, the
following frame should be sent:
Decimal
Hexa.
Number
Text
Unit
address
address
of words
2560
A00
2
Input E1, option ES 1
2562
A02
2
Input E2, option ES 1
2564
A04
2
Input E3, option ES 2
2566
A06
2
inputE4, option ES 2
2568
A08
2
Input E5, option ES 3
2570
A0A
2
Input E6, option ES 3
Slave
05
Function
06
High-order
address
04
Low-order
address
00
High-order
word N°
10
Low-order
word N°
00
CRC 16
84BE
Slave
05
Function
06
High-order
address
06
Low-order
address
00
Values
0000
CRC 16
88C6
Summary of Contents for Rudolf R-DPA96 A
Page 25: ...25 R DPA96 A AN RUDOLF Ref 876 583 A DPA96A DPA96A DPA96A DPA96A x 1 x 2 x 3 x 4 OPERATION...
Page 27: ...27 R DPA96 A AN RUDOLF Ref 876 583 A DPA96A DPA96A DPA96A x 9 x 10 x 11 DPA96A x 12 OPERATION...
Page 28: ...28 RUDOLF Ref 876 583 A R DPA96 A AN DPA96A DPA96A DPA96A x 3 x 1 x 2 OPERATION...
Page 43: ...43 RUDOLF Ref 876 584 A...
Page 44: ...44 RUDOLF Ref 876 584 A...
Page 53: ...53 SOCOMEC R f 876 585 A...
Page 54: ...54 SOCOMEC R f 876 585 A...
Page 129: ...129 RUDOLF Ref 876 341 A...
Page 130: ...130 RUDOLF Ref 876 341 A...
Page 139: ...139 RUDOLF Ref 876 586 A...
Page 140: ...140 RUDOLF Ref 876 586 A...
Page 152: ...152 RUDOLF Ref 876 587 A...
Page 168: ...OPERATION DPA96A DPA96A RUDOLF Ref 876 588 A R DPA96 A AN R Module 7 Memory 168...