Renovent Excellent 450 614784-F
11.1 Connections connectors
Connector X1
EBus connector X1
Two-pole screw connector.
Set ex factory as eBus connector; after modifying parameter 8 in
the Settings menu, also suitable as OpenTherm connector (see
§11.3).
Only suitable for low voltage.
Note:
)RUWKHH%XV$SSOLFDWLRQWKLVFRQQHFWRULVSRODULW\VSHFL¿F
Connector X2
Modular connector X2 for rpm control
Modular connector type RJ-12.
Only suitable for low voltage
Connector X14 (only for Plus version)
Connector X14 for connecting postheater
7ZRSROH VFUHZ FRQQHFWRU DFFHVVLEOH DIWHU WDNLQJ Rႇ GLVSOD\
cover).
Ex factory this connector is not activated; after changing param-
HWHULQWKHVHWWLQJVPHQXRI³´WR³´SUHKHDWHURU³´SRVW
-
heater), this connector can be used for connecting the postheater
or preheater
Maximum rated power is 1000W.
Note:
The postheater temperature sensor must also be con-
nected to X15-7 and X15-8.
For the Plus version, use the additionally mounted pull relief in the
display cover to feed the 230 V cable to the postheater.
Connector X15 (only for Plus version)
Chapter 11 Electric connections accessories
Connector X15
SROH
for connecting special versions
Connection Application
1 & 2
(input 1)
Stepnr. 15 = 0: normally open contact
(= factory setting) §11.7)
Stepnr.
15 = 1: 0 - 10V input 1; X15-1=GND &
15 - 2 = 0 - 10V (see §11.8)
Stepnr.
15 = 2: normally closed contact
Stepnr.
15 = 3: input 1/ bypas open
¼
12V;
bypass closed
¼
0V
Stepnr.
15 = 4: input 1/ bypas open
¼
0V;
bypass closed
¼
12V
3 & 4
(input 2)
Stepnr.
21 = 0: normally open contact
Stepnr.
9LQSXW
(= factory setting)
(see §11.8).
Stepnr.
21 = 2: normally closed contact
Stepnr.
21 = 3: input 2/ bypas open
¼
12V;
bypass closed
¼
0V
Stepnr.
21 = 4: input 2/ bypas open
¼
0V;
bypass closed
¼
12V
5 & 6
Conn. 24 volt
, 4.5 VA maximum (5 = ground , 6 = +)
7 & 8
Connection postheater sensor or and outdoor
JHRKHDWH[FKDQJHU
9
Control signal valve 0 or 10 V
( 9 = + , 5 = ground)
Not suitable
IRU9
1 2 3 4 5 6 7 8 9
;