background image

Page 

5

 of 

5

 

 

 

RPCOL   

 

 

 

 

REV 3:    September 2010 

 

 

RECHARGING PROCEDURE FOR BRITANNIA RANGE CARTRIDGE OPERATED LIQUID MODELS 

 
 

MODEL NO'S:  BW6, BW9, BT6, BT9, BAF9, BAQ6, BAQ9, BTU3, BTU6 

 
 

THESE RECHARGE PROCEDURES SHOULD BE USED IF COMPLETE OR PARTIAL USE OF THE 

EXTINGUISHER IS SUSPECTED.

 

 
 
1.

 

Check for signs of damage or corrosion to extinguisher if found.  Do not continue recharge 
procedure, mark extinguisher 'condemned' and inform user.   Ensure instruction label is 
legible, rectify as necessary. 

 
2.

 

Ensure pressure is relieved by inverting extinguisher and squeezing the levers together 
slowly (whilst pointing nozzle down and away). 

 

 

3.

 

Ensure your body/head is not directly over extinguisher. Loosen headcap, using nutring 
spanner [Part Ref: HCS] (do not use hammer or other blunt instrument).  Remove headcap 
slowly, allowing residual pressure to escape through vent holes. 

 
4.

 

Empty residual liquid from extinguisher and rinse with clean water. 

 
5.

 

Inspect the internal lining for signs of detachment, cracks or corrosion. If found, remove 
from service and replace. 

 
6.

 

Refill the cylinder to the correct level (making allowance for any additives, if applicable).  
Then add foam concentrate/additives, ensuring manufacturers specifications are met. 

 
7.

 

Remove CO

2

 cartridge and discard, inspect headcap and components, replacing any parts 

that appear damaged or show signs of deterioration.  Blow through nozzle whilst opening 
and closing valve. If signs of blockage, rectify. 

 
8.

 

Fit safety pin and seal (in accordance with service colour code). Checkweigh replacement 
CO

2

 cartridge and fit to headcap, ensuring it is the correct size and type as supplied by the 

manufacturer. 

 
9.

 

Fit new headcap 'O' ring and check nutring vent holes and refit headcap assembly to 
extinguisher body using nutring spanner [Part Ref: HCS]. 

 
10.

 

Record recharge details on service label, including new weight, and return extinguisher to 
original position. 

 

 

Summary of Contents for BW6

Page 1: ...Page 1 of 5 BRITANNIA RANGE EXTINGUISHER SERVICING MAINTENANCE INSTRUCTIONS Cartridge Operated Water Based extinguishers ...

Page 2: ...e security and suitability of the hanging bracket and that the extinguisher is of the right type for the prevalent risk If the extinguisher is to be sited in a hazardous corrosive environment i e marine use the inspection periods should be more frequent The effects of the environment should be considered with particular reference to corrosion and legibility of marking instructions If there is corr...

Page 3: ...ore than 10 of the content weight 5 Ensure your body head is not directly over extinguisher Remove the headcap using the nutring spanner Part Ref HCS warning should pressure issue from vents allow pressure to escape before complete removal of headcap Do not use blunt instrument i e screw driver etc 6 Check liquid level ensuring level is below the hanging bracket Add or remove liquid to correct lev...

Page 4: ...and hose clips for wear cuts or abrasions Replace if necessary 13 Refit safety pin service indicator and seal in accordance with service colour code Refit original or new CO2 cartridge 14 Clean extinguisher neck threads and refit headcap using nutring spanner Part Ref HCS do not use blunt instrument 15 Fill in details of service on service label including extinguisher weight using indelible pen Cl...

Page 5: ...t holes 4 Empty residual liquid from extinguisher and rinse with clean water 5 Inspect the internal lining for signs of detachment cracks or corrosion If found remove from service and replace 6 Refill the cylinder to the correct level making allowance for any additives if applicable Then add foam concentrate additives ensuring manufacturers specifications are met 7 Remove CO2 cartridge and discard...

Reviews: