It is not necessary to cut the ducts
If L is between
1175 - 1475mm
(1 extension)
1925 - 2225mm
(2 extension)
2675 - 2975mm
(3 extension)
3425 - 3725mm
(4 extension)
It will be necessary to cut the ducts
If L is between
725 - 1175mm
(1 extension)
1475 - 1925mm
(2 extension)
2225 - 2675mm
(3 extension)
2975 - 3425mm
(4 extension)
3725 - 4000mm
(5 extension)
It is necessary to shorten the assembly by cutting the first
extension duct assembly eg. L = 1000mm - remove 175mm
from the air and flue ducts (1175 – 1000 = 175mm).
NOTE:
Extension duct measurements do not include the
socketed end. Unless specifically instructed the socketed end
must not be removed.
Fix the flue ducts together before fixing the surrounding air duct,
the cut ducts fit into the terminal assembly.
11.10 Fitting the Flue Assembly with Access to the Terminal.
Prepare the flue duct assembly as described in Section 11.8.
Apply the plastic tape to the air duct to be in contact with the
external brickwork.
From inside push the assembly through the wall. Align the flue
turret and push fully onto the spigot on the appliance. Tighten
the clamping ring. Refer to Fig.27.
Make good the internal wall face and the external brickwork or
rendering.
11.11 Fitting of the Flue Assembly without access to the Terminal.
The rubber gasket kit is available from Worcester Heat Systems.
NOTE:
A larger diameter opening in the wall is required. Refer to
Table 2.
16
Fig. 24. Extension duct
L
Fixing screw
Flue
turret
assembly
Appliance casing
Terminal
assembly
Fixing screw
Ducts of equal length
Fig. 25. Flue duct length - side
L
Flue
turret
assembly
Terminal
assembly
Flue
turret
assembly
Terminal
assembly
Fig. 26. Flue duct length - rear
L
Summary of Contents for RD 628
Page 34: ...34 1 2 3 4 7 5 6 8 9 10 11 12 4 15 13 16 19 14 17 18 20 22 23 21 ...
Page 45: ...45 ...
Page 46: ...46 ...
Page 47: ...47 ...
Page 51: ......
Page 53: ......
Page 55: ...L2 0mm ...
Page 57: ......
Page 58: ...RD 628 USER INSTRUCTIONS CUSTOMER CARE GUIDE G C NUMBER 47 108 14 ...
Page 71: ...14 ...