Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
68
Cooler Operation
(cont.)
Water Inlet Solenoid Operation
(cont.)
If power present and inlet solenoid doesn't open:
•
Check the water inlet solenoid wire loom and connections.
Isolate power and check the
Water Inlet Solenoid
coil resistance (4.1 kOhms).
INLET VALVE - NEUTRAL
INLET VALVE - ACTIVE
OFF
10 A
V
COM
1000V- - -
750V
V
kOHMS
Multimeter
FUSED
3.9
•
Check if the water inlet solenoid is blocked.
Replace water inlet solenoid.