285 Issue 1 - Service Manual - Iceberg
37
13.0 Dip Switches & Potentiometer
13.1 Dip Switch Settings
Dip Switch on the main control board are parameters that distinguish what the Iceberg
configuration is. Detailed descriptions of the parameters are on the chart below.
1-0-0-0
1 Wall Control to 4 zones will run all 4 fans simultaneously
0-1-0-0
Functional testing program will run each individual component testing purposes.
0-1-0-1
Installation Check: This function will allow the unit to open the winter seal and open
the water solenoid will open and the tank will begin to fill with water.
Turn power back onto the Brivis Iceberg™ and the “
Installation Check
” will start
automatically and proceed through the following sequence
A) WinterSeal will open.
B) Water solenoid will open and tank will begin to fill with water.
C) When high level is reached the solenoid will close and drain pump will run for 2
minutes
D) After 2 minutes item ‘b’ will repeat followed by ‘c’
E) If there are no issue with the water supply and primary drain the Winter Seal
will close
0-0-1-0
Activate drain pump will come on
0-0-1-1
Activate the circulation pump
0-0-0-1
Activate the water solenoid valve
Positions
Descriptions
1-0-0-0
1 Wall controller for 4 zones (CPI= All Fans)
1-1-0-0
N/A
1-1-1-0
N/A
1-1-1-1
N/A
0-1-0-0
FUNCTIONAL TESTING PROGRAM
0-1-0-1
INSTALLATION Check
0-1-1-0
cleaning program
0-0-1-0
Activate drain pump
0-0-1-1
activate water supply pump
0-0-0-1
open solenoid
0-0-0-0
N/A